Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Woodward The QuickTrip valves are controlled with the independent trip relay

Control Input

The QuickTrip valves are controlled with the independent trip relay outputs from a trip system logic solver

such as the Woodward ProTechTPS.

Note: When used with the ProTechTPS, external power is not necessary for these inputs. All voltage

and isolation is provided within the ProTechTPS (24 VDC, 0.5 A).

Trip Points:

• If the input voltage drops below14 VDC, then the input will detect a Trip state.

• If the input voltage rises above 15 VDC, then the input will detect a Run state.

Control Input Isolation: 500 VAC from input to chassis.

Wiring Requirements

• Keep this and all other low level signal cables separated from input power cables to avoid

unnecessary coupling (noise) between them.

• Wire Gauge Range: 0.8 to 1.3 mm² / 16 to 28 AWG stranded wire.

• Shielding: The control inputs are unshielded; however, the wires should be kept in a twisted

configuration for noise immunity.

Position Feedback

There are two outputs for valve position feedback on each of the QuickTrip’s three valve modules (12

outputs total). Each of the two outputs features redundant connections. Both TRIP outputs and both RUN

outputs operate as normally open. The outputs can be wired to either switch load from positive supply or

switch load to ground. The user must supply the external 24 V supply for the output to function properly. If

using the Woodward ProTech TPS logic solver, the voltage may be supplied using the on-board discrete

power terminals (24 VDC, 0.050 A).

Woodward QuickTrip Electro-Hydraulic Trip Block Assembly Control Input

Wiring Strain Relief

Tie down points and ratcheting tie wraps are provided to secure the wiring to the PCB mounting plate.

This helps prevent wire strain from being transmitted to the connection at the terminal block and to keep

the wiring from chafing on the cover when tightening and under vibration. Failure to secure the wiring

could result in intermittent connections resulting in intermittent operation or shutdown conditions. Allow for

additional wire service length between the tie down points and the connectors to reduce strain on the wire

at the connector interface and to allow the black pluggable connector to be removed.

Shield Installation Notes

• Wires exposed beyond the shield should be as short as possible, not exceeding 50 mm (2 inches).

• The shield termination wire (or drain wire) should be kept as short as possible, not exceeding 50 mm

(2 inches), and the diameter should be maximized where possible.

• Installations with severe electromagnetic interference (EMI) may require additional shielding

precautions. Contact Woodward for more information.

• Do not ground shield on both ends, except where permitted by the control wiring diagram.

Failure to provide shielding can produce future conditions that are difficult to diagnose. Proper shielding at

the time of installation is required to ensure satisfactory operation of the product.

Woodward QuickTrip Electro-Hydraulic Trip Block

Wire Cross-Sectional Area Voltage Drop

A standard wire cross-sectional area voltage drop at maximum ambient temperature is provided in Table

3-6 and Table 3-7 to assist with cable selection.

Example of Voltage Drop Calculation Using Wire Cross-Sectional Area

0.067

Example #1. one power supply per module (3x power supplies): A 2.5mm2 wire will drop 0.044 V/m at 2.6 A at

maximum ambient temperature. Using 30m between the QuickTrip and the power supply would provide a

voltage drop of 30 x 0.044 = 1.32V.

Example #2. one power supply for all three modules (1x power supply): A 2.5mm2 wires will drop 0.132 V/m

at 7.8 A at maximum ambient temperature. Using 30m between the QuickTrip and the power supply would

provide a voltage drop of 30 x 0.132 = 3.96V.

It is very important to ensure the voltage at the QuickTrip’s input terminal is within the product power input

specification to achieve the maximum performance.

A guideline for allowable voltage drop is to size the wire for <10% of the nominal voltage under maximum

transient conditions.

Woodward Voltage Drop Calculation Using American Wire Gauge

Voltage Drop Calculation Using American Wire Gauge

Example #1. one power supply per module (3x power supplies): A 18 AWG wire will drop 0.042 V/ft at 2.6

A at maximum ambient temperature. Using 100 feet between the QuickTrip and the power supply would

provide a voltage drop of 100×0.042 = 4.2V.

Example #2. one power supply for all three modules (1x power supply): A 18 AWG wire will drop 0.125

V/ft at 7.8 A at maximum ambient temperature. Using 100 feet between the QuickTrip and the power

supply would provide a voltage drop of 100×0.125 = 12.5V.

It is very important to ensure the voltage at the QuickTrip’s input terminal is within the product power

input specification to achieve maximum performance.

Extended Power Input

The Power Wiring Requirements section above specifies the maximum length of 30 meters between the

power source and the QuickTrip. Installations that require a longer power cable run also require a much

larger wire gauge to account for voltage drop. Figure 3-6 below gives a possible solution for installations

required to run at longer distances.

Woodward QuickTrip Electro-Hydraulic Trip Block Assembly Input Power

Input Power

The QuickTrip requires a power source capable of supplying the necessary output voltage and current

at full transient conditions. The maximum power in watts (W) of a DC source can be calculated by

multiplying the rated output voltage by the maximum output current capability. The calculated power

rating of the supply should be greater than or equal to QuickTrip requirements. The electrical power

supply should be able to provide 8 A (or 2.6 A per channel) at 24 VDC continuously.

Cable selection and sizing is critical to avoid power loss during operation. The power supply

input at the electronic module input terminal must always provide the required nominal voltage to operate

the valve.

The input power wires must comply with local code requirements and be of sufficient size such that the

power supply voltage minus the IR loss in the two lead wires to the QuickTrip valve electronics module

does not drop below the input minimum voltage requirement.

The QuickTrip is not equipped with an input power disconnect. A means of disconnecting input power to

the QuickTrip must be provided for safe installation and servicing.

The QuickTrip is not equipped with input power protection. A means of protecting input power to the

QuickTrip must be provided. Breakers or fuses are intended to protect installation wiring and power

sources from faults in the QuickTrip or wiring. A circuit breaker meeting the requirements listed in the

table below, or a separate protection with the appropriate ratings, may be used for this purpose.

Circuit protection, which isolates both positive and negative leads, is recommended.

Refer to the table below for recommended fuse ratings or circuit breakers.

ABB AX411/511010 Conductivity Transmitter

• Cost effective

– select one or two conductivity inputs or

combine conductivity and pH/Redox (ORP) in

one analyzer

– integral PID controller (AX410)

• Reduced installation cost

– easy access terminations; reduced panel space

• High functionality at minimum cost

– conductivity, resistivity, difference, ratio,

%passage, % rejection and inferred pH calculations

• Expanded monitoring and control

– add-on option board provides a total of five

alarm relays and four current outputs

– service logbook providing historical data

• Energy saving

– high visibility, backlit display with auto switch-off function

• Reduced yearly maintenance costs

– 30V DC option negates the need for costly safety tests

• Wide range of applicability

– water and waste water treatment

– power, pure water

– semiconductors

– chemicals

– pharmaceuticals

– pulp & pape

The AX400 Series

The AX400 analyzers incorporate the latest technology to

provide highly reliable, flexible, feature-packed devices that

satisfy a diverse range of process monitoring and control

applications. The complete range encompasses solutions for

pH/Redox (ORP), conductivity and dissolved oxygen.

Models AX41x and AX45x enable continuous measurements of

one or two low-level conductivity points with simultaneous local

display and retransmission. The analyzers are used with ABB

2-electrode conductivity cells providing measurements with

exceptional accuracy and performance.

Model AX45x analyzers are dedicated to United States

Pharmacopoeia <645>.

AX400 Series analyzers are available for either wall-/pipe- or

panel-mounting and are rated to IP66 (NEMA4X).

Model Numbers about ABB AX410. AX411. AX416. AX450 and AX455 series:

AX410/10001;AX410/50001;AX410/100010/STD;AX411/10001;AX411/500010/STD;

AX416/10001;AX416/50001;AX430/10001;AX460/10001;AX411/10001;

AX431/10001;AX461/10001;AX413/10001;AX433/10001;AX463/10001;

AX436/10001;AX466/10001;AX410/20001;AX430/20001;AX460/20001;AX410/15001;

AX430/15001;AX460/15001;AX410/16001;AX430/16001;AX460/16001;

AX416/50001;AX410.2.0.0.0.1;AX400-0295;AX400-0365;AX410/1000C;AX410/10101;

AX410/50001;AX410/5000C;AX410/5200C;AX410/500010/STD;AX416/50001;

AX430/1000C;AX430/5000C;AX430/20001/STD;AX433/11001;AX460/10001;

AX460/1000C;AX460/10101;AX460/2000C;AX460/5000C;AX460/5200C;AX466/1000C;

AX466/5000C;

Woodward QuickTrip Electro-Hydraulic Trip Block Assembly Specifications

Specifications

Physical and Performance Specifications

Solenoid Response Time: < 50 ms*

Failsafe Operation: Internal return spring on each solenoid valve

Weight: 110 kg (242 lb)

Mounting: Vertical mounting

* Solenoid response time represents the valve trip time and is defined as the time from when the solenoid

is de-energized to the time when the valves are at the full open position.

Environmental Specifications

Ambient Temperature: (–40 to +85) °C / (–40 to +185) °F

Ex nA nC Minimum Ambient

Temperature: -20 °C (-4 °F)

Vibration Resistance: MIL-STD 810F, M514.5A, Cat. 4

(0.015 G²/Hz, 1.04 Grms)

Shock Resistance: US MIL-STD-810C method 516.2. procedure 1

(10 G Peak, 11 ms duration, saw tooth)

Corrosion Resistance: Two-part epoxy paint coating. Designed for outdoor conditions.

Ingress Protection

(IEC 60529. IEC 60079-0): IP66

Electrical Specifications

Supply Voltage: 24 VDC nominal ± 10% (use cable at least 0.8mm² / 18 AWG)

Current Consumption: 8 A max (2.6 A per channel max) at steady state @ 24 V

Control Input Voltage: 0-32 VDC, 20 mA max

Feedback Output Signal: Resistive: 2 A @ 28 VDC, max 32 VDC

Inductive: 0.5 A @ 28 VDC (max. 0.2 Henry)

Supply Voltage Connections: Terminal suitable for 0.8 to 3.3 mm² or 18 to 12 AWG stranded wire

Control Input and Discrete

Removable terminal suitable for 0.8 to 3.3 mm² or 18 to 12 AWG

stranded wire

Connections:

Cable Entries: 3 X 0.750”-14 NPT

1 Ground

Woodward Chemically Resistant Versions

Chemically Resistant Versions

For steam turbine applications where lube oil contains harsh chemical contaminants (ammonia, hydrogen

sulfide, etc.), a chemically resistant version of the QuickTrip has been developed. Chemically resistant

versions feature best-in-class seals in all wetted locations within the trip block assembly. Chemically

resistant versions provide an optimal solution for extreme chemical resistance while still maintaining

QuickTrip operating pressure and temperature ranges. Please contact Woodward for available models

and information regarding chemical resistance for specific applications.

Rotary Trip Valves

All three of the QuickTrip’s trip valves are spring return, two position rotary valves. When any of the

hydraulic valves is in its closed position, the ports in the valve are blocked preventing hydraulic flow

through the valve. As a valve rotates to the tripped position, the ports open and the trip header pressure

is connected to either the drain, or the inlet ports of another one of the valves. The combined action of the

three valves results in trip header pressure being connected to drain only when 2 or 3 valves are tripped.

If the unit detects any shutdown condition or loss of power occurs, the trip valve return springs will force

the valves to the fail-safe / tripped position.

Woodward Electronic Driver Modules (PCB)

Electric Valve Actuators

The QuickTrip uses a set of three unique rotary solenoids called limited angle torquers (LAT). The

permanent magnet rotor is directly coupled to the trip valve.

The position of the valves is sensed by two limit switches present on each of the electrical modules.

These limit switches are located on both the closed and tripped positions of the valves, allowing the user

to easily determine the position of each valve.

Electronic Driver Modules (PCB)

The printed circuit boards (PCB) are mounted on of the top of each valve module. The PCB(s) performs

the following tasks:

• Trip demand input

• Dual redundant power inputs

• Valve position feedback discrete outputs

• Visual valve position indication

Discrete outputs are provided for position feedback indication of each valve module. Within each valve

module, there are also four LEDs that indicate the current condition of the module as well as power

supply health. These LEDs are viewable through the module covers’ transparent sight window.

Woodward QuickTrip Electro-Hydraulic Trip Block Assembly Dirt Tolerance

Valve Status (local & remote)

Each valve solenoid accepts power for one or two (redundant) power sources and has the following

status indications to assist operators with understanding the status and health of each valve.

• Valve Open—Local LED (red)

• Valve Open—Limit Switch

• Valve Closed—Local LED (green)

• Valve Closed—Limit Switch

• Power Supply #1 Healthy—Local LED (blue)

• Power Supply #2 Healthy—Local LED (blue)

Redundancy/Availability

Designed for use in critical gas and steam turbine applications where turbine up time is important, the

QuickTrip uses three isolated solenoid valves designed to be driven by a triple modular redundant 2-out

of-3 voting based safety logic solver. Each isolated solenoid valve uses redundant power supply inputs to

increase both system reliability and availability. Note: only one power source is required to

power/energize each of the isolated solenoid valves.

On-Line Repairable

The QuickTrip’s modular design allows independent repair/replacement of each valve’s solenoid,

electrical module, and associated power supplies and wiring to increase both system reliability and

availability. Note: only one power source is required to power/energize each of the isolated

solenoid valves.

Search for products

Back to Top
Product has been added to your cart