Prosoft MVI56-104S IEC 60870-5-104 Ethernet Server Communication Module

The IEC 60870-5-104 Server functionality supported by the module includes: 

 The IEC 60870-5-104 communication driver is built in accordance to the approved 

IEC specification 

 The module functions as a Server on the network supporting data read/write 

commands from an IEC 60870-5-104 client on the network 

 One TCP server socket 

 Supports unsolicited messages, either cyclic or spontaneous (cyclic rate is 

configurable) 

 Supports clock synchronization commands from client or from the ControlLogix 

processor 

 Supports Group interrogation (Global, General 1 to 16, Global Counters, Counters 

1 to 4) 

 Event timestamping configurable by type (None, 24 bit, 56 bit) 

 Event queue supports 99 points for each data type 

 Optional user defined list of acceptable client host IP addresses 

 Configurable Common ASDU address (sector) and Information Object Address 

 An IEC Interoperability Document for the MVI56 is available which fully documents 

data types supported by the module

Omron CQM1H Programmable Controller

The CQM1H’s rack-less modular design lets you customize your control

system by adding “inner boards” for advanced functions, as well as

specialized I/O and communications modules.

CQM1H offers the most flexibility of all PLC systems in its class.

• 4 different base CPUs to choose from; 16 DC inputs built in;

expands up to 512 points

• No separate backplane required

• Inner Boards allow “customized” configuration of the CPU

• Serial communications inner board supports protocol macro feature

for communication with third-party serial devices

• Supports all existing and new CQM1 I/O and specialized I/O modules

• Optional memory cassettes allow backup of sensitive data, provides

a real-time clock

• ControllerLink network transmits 8 kword data packets at up to 2 Mbps;

32 nodes

• Advanced instruction set includes PID, floating point math, protocol

macro instructions and more

• CompoBus/S, SYSMAC BUS and AS-interface masters support remote I/O

• Up to 15.2 kwords of program memory

Basic Configuration

Select the CPU and I/O modules (discrete, analog and dedicated special

function types) then determine the power supply based on the current

consumption. The I/O Control and Interface adapters give you the option

of dividing the CPU and I/O system into two narrower units than the

examples shown below. The CQM1H-CPU51/CPU61 models offer space-saving

position and motion control solutions as well as additional analog and serial

communications capabilities right at the CPU.

Emerson Fisher™ 377 Features

Features

• Cost Effective—Single trip valve construction

reduces costs and spare part requirements of those

systems using three separate switching valves to

perform the failure functions. A single trip valve

greatly simplifies piping requirements.

• Ease of Mode Conversion—Conversion to any of the

fail modes requires only minor hookup changes.

• Adjustable Trip Valve—The trip point is adjustable

for specific supply pressure requirements.

• Reliable Operation—The trip valve design includes

large diaphragm areas and few moving parts for

efficient performance, minimum maintenance, and

long service life.

Specifications

Available Configurations

When supply pressure falls below the trip point,

377D Trip Valve: Fails actuator piston down. Includes

check valve and volume tank.

377L Trip Valve: Locks actuator piston in the last

position.

377U Trip Valve: Fails actuator piston up. Includes

check valve and volume tank.

377CW Trip Valve: Fails fully clockwise to close the

valve. Requires check valve and volume tank. Trip

valve moves piston to either up/down position and

requires actuator configuration for actual clockwise

movement.

377CCW Trip Valve: Fails fully counterclockwise to

close the valve. Requires check valve and volume

tank. Trip valve moves piston to either up/down

position and requires actuator configuration for

actual counterclockwise movement.

All 377 trip valves can be converted to any of the

above fail modes with minor hookup changes

Emerson Fisher™ 377 Trip Valve

Fisher™ 377 Trip Valve

Fisher 377 pressure‐sensing trip valves are for control

applications where a specific valve/actuator action is

required when supply pressure falls below a specific

point. When supply pressure falls below the trip point

(see figure 1), the trip valve causes the actuator to fail

up, lock in the last position, or fail down. When the

supply pressure rises above the trip point, the 377 trip

valve automatically resets, allowing the system to

return to normal operation. The trip valve can be

top‐mounted on a manifold, yoke‐mounted, or

bracket‐mounted to match the application

requirements. 377 trip valves can be used with Fisher

480. 585C, 685. 1061. 1066. 1069. and Bettis™ G

Series piston actuators.

Prosoft MVI56-104S General specifications

General specifications include:

 User-definable database memory usage, based on data types and point counts

 Protocol implementation conforms to the IEC 60870-5-104 specification with fully-configurable

parameters

 SNTP (Simple Network Time Protocol) timestamping for detailed logging of data transactions (events)

IEC 60870-5-104 Server Specifications 

Operating in the Server mode, the module accepts commands from a Client(s) to 

read/write data stored in the module’s internal registers. This data is easily and 

continuously transferred between the MVI56-104S, Edition 2 module and the 

ControlLogix processor’s data registers. 

Prosoft MVI56-104S General Specifications – 104S

General Specifications – 104S

Operating in server mode (only), the 104S protocol implementation accepts commands

from an IEC-60870-5-104 Client to read data stored in or write data into the gateway’s

internal database memory registers. The 104S implementation is also capable of generating

unsolicited messages. Unsolicited messages can be either spontaneous (event-driven) or

cyclic (timing-driven) communication.

The remote Client device uses the fully-configurable gateway memory database to control

outputs and monitor inputs to devices on the

IEC 104 network.  Changes to the gateway database can also be used to transfer monitoring

and control data to devices connected to

the gateway using another installed network protocol. The 104S gateway thus provides a data

transfer solution between an IEC 60870

5-104 Ethernet network and other serial and Ethernet network protocols, as well as proprietary interfaces.

Prosoft MVI56-104S IEC 60870-5-104 Ethernet Server Communication Module with Edition 2 Support

The MVI56 IEC 60870-5-104 Server Communication Module allows

ControlLogix compatible processors to interface easily with IEC 60870-5

104 protocol-compatible hosts.

The MVI56-104S module acts as an input/output module between the IEC

60870-5-104 Ethernet network and the ControlLogix processor. Data

transfer between the module and the processor is asynchronous from the

actions on the network. Databases are defined by the user for the module to

hold data as required by the protocol.

General Specifications

 Single Slot – 1756 backplane-compatible

 The module is recognized as an Input/Output module and has access to

processor memory for data transfer between processor and module.

 Ladder Logic is used for data transfer between module and processor.

Sample ladder file included.

 Configuration data obtained from configuration text file downloaded to module. 

Sample configuration file included

 Local or remote rack

Prosoft MVI56-EGD Features and Benefits

Features and Benefits

GE Fanuc Automation and GE Drive Systems developed an Ethernet

Global Data, or EGD, exchange for PLC and computer data in 1998.

Ethernet Global Data (EGD) offers versatility where a mix of control

devices requires cooperation with each other. This involves sharing

of information across the applications regardless of device or network

type, often at high speed, and with high reliability. High reliability

means fewer communication failures and having the ability to detect

failures upon occurrence. Particular emphasis is delivered for

applications requiring periodic or frequent updates and time

synchronization of devices. The protocol supports Unicast, Broadcast

and Multicast group messaging. Efficiency is based on the fact each

device on the network can produce these types of messages and

each device determines which of these messages to consume.

Prosoft MVI56-EGD GE Ethernet Global Data Communication Module

MVI56-EGD

The Ethernet Global Data (EGD) module can be used to interface

many different protocols with EGD devices. The EGD driver supports

both the producer/consumer service port (18246) and the command

service port (7937) using the UDP protocol over an IP network. The

user defines the data to be produced and consumed in a

configuration file downloaded to the module.

General Specifications

• Single Slot – 1756 backplane compatible

• The module is recognized as an Input/Output module and has

access to processor memory for data transfer between

processor and module

• Ladder Logic is used for data transfer between module and

processor. Sample ladder file included.

• Configuration data obtained from configuration text file

downloaded to module. Sample configuration file included

• Local or remote rack

Prosoft MVI56-LTQ Functional Specifications

Functional Specifications

 Support for the storage and transfer of up to 150 valves to the ControlLogix

processor’s controller tags

 Emulates Limitorque’s Port A/B polling scheme using both ports on the module

 Supports the following valves

o MX/DDC Modbus

o UEC-3-DDC Modbus

o DDC-100M I/O module

o DDC-100M field unit

o Valvcon IVO (unit in multi-drop mode only)

 Software configuration

o Baud rate: 1200 to 115200

o Message response timeout

o Number of active slaves

o Last state on communication failure for valve data

o Network polling scheme

o Active slave table (bit mapped)

o Use of CTS module line option

 Support command

o Continuously polled

o Read registers 40008 to 40013. optional 40055 or 40006/40007

o Commands: open, stop, close, initiate network ESD, terminate network ESD,

engage contactors 1 to 6. disengage contactors 1 to 6. position valve (0 to 100%)

 Data returned to the processor for each valve

o Valve position

o Status register

o Fault register

o Digital outputs

o Digital inputs registers 1 and 2

o Communication error code

o Communication poll counter

o Special polled registers