Conventional and older technology UV/IR detectors, using
narrow band 4.3 micron IR sensors, will not respond to smoky
fires or if the detector lens is contaminated with oil and
other substances since both UV and 4.3 micron signals are
attenuated, obscured or absorbed by thick smoke or detector
lens contaminations. All UV sensors will be attenuated to some
degree. Also, these old technology UV/IR detectors will not alarm
to any fire if they are installed behind ordinary window glass.
Dual microprocessors provide a high level of fail-safe operation combined with fast and reliable
performance.The master microprocessor performs high-speed digital sampling and signal
processing calculations whilst the slave microprocessor handles various sensor data, performs
communications, self-diagnostics and provides interface versatility and additional memory for
storing event log and FirePic™ data. The FS20X detector has a detection range in excess of 60 m
(200 feet) (very high sensitivity setting) for the detection of a 0.1m2 (one square-foot) Heptane
reference fire and has a cone of vision greater in volumetric coverage than most UV/IR detectors.