BASEPLATE IMPLEMENTATION
A grouping of up to four baseplates per FCM (pair)
can be connected together, for mounting of up to 32
modules (30FBMs and 2 FCMs). Multiple groups of
baseplates can be connected to the Ethernet trunk
Fieldbus, either directly (via Ethernet connectors) or
through one or more multiport fiber optic converters
(hubs). (Refer to PSS 21H-2W1 B3 for information on
the various DIN rail mounted FBM subsystem
communication topologies). Module Fieldbus
interconnection between baseplates is made by
shielded twisted-pair cable for local configurations
and/or by fiber optic cable for remote configurations.
Using fiber optic topologies (refer to
PSS21H-2W1B3), baseplates can be separated up
to 10 km (6.2 mi).
Figure 1 shows baseplate implementation using only
shielded twisted-pair cable connections. This
configuration is used when the four (maximum)
baseplates are mounted in the same general location.
Using shielded twisted-pair cable, the baseplates can
be interconnected up to 60 m (196 ft) total cable
distance. Shielded twisted-pair cables are available in
lengths of 0.25 m (10 in), 1 m (3.3 ft), 3 m (9.9 ft), 5 m
(16.5 ft), 10 m (33 ft), 20 m (66 ft), 30 m (99 ft) and
60m (198 ft), allowing placement of the baseplates
(up to four in a group) in one or more enclosures.