Operation and configuration
LED indicator functions
The EAFR-101C contains 16 indication LEDs . A user definable text
pocket can be slid in under the label for identifying each LED func
tion (except POWER and ERROR LEDs) . LEDs are located at the
front plate of the relay for clear viewing without a need for opening
doors .
During power up, the relay performs an LED test . All LEDs are
turned on for two seconds and then off . Only the blue POWER LED
will remain on . After powered up, the relay goes into protection
mode in 50 ms even while the LED test is being performed .
During normal operation, the blue power LED is ON, as are any CB
open/close status LED’s for connected CB’s .
The sensor LEDs are off during the inactive condition . If a point arc
sensor is activated, the corresponding sensor channel LED will turn
on if the activation is longer than 1 .5 ms . The sensor LED activation
function is latched (steady light) . To clear the LED, the “SET” button
should be pressed .
In case of a loose sensor wire and binary input wires or configura
tion mismatch (new sensor attached without running auto-configu
ration system setup (see Section 3 .3 .1) situation, the corresponding
LED for that sensor will start flashing and the ERROR LED will
activate .