Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Bently Nevada SCOUT220-IS and SCOUT240-IS Portable

Description

SCOUT220IS and SCOUT240IS are intrinsically safe portable data

analyzer solutions designed to monitor machinery conditions in

hazardous environments. Both are rated ATEX Zone 1 / Zone 21

(for gases and non-conductive dust) and CSA Class 1 / Div 1.

These small form-factor, rugged devices take vibration

recordings and upload the collected data for detailed analysis in System 1.

This is a two-part solution. The SCOUT data acquisition module

uses Bluetooth to communicate with a wireless, industrial

handheld device running the S1 Collector app.

Vibration recordings are viewed and stored on the handheld

device. We offer these devices with hazardous area ratings up to

Zone 1/21 & Div 1. The handheld runs the Android OS, so you can

also use it like any smartphone or tablet to take pictures and

video, send text messages, check email, make phone calls, track

your location, create SOS alerts, and run other enterprise apps.

The high performance data acquisition module provides long

battery life, yet is light & rugged. It hangs out-of-the-way on a

shoulder strap, allowing you to focus on your job and move

safely between machines. 

Bently Nevada SCOUT200 series System 1 software

System 1 software,your plantwide solution

Use System 1* to prepare routes, analyze

data, detect long-term trends, set and

detect alarms. Then synchronize data

with your SCOUT handheld using WiFi, file

transfer, cellular network, or a USB cable. But

System 1 doesn’t stop there, it’s the same powerful package

that’s coupled with a broad range of Bently Nevada condition

monitoring and protection products. One source of the truth,

modern and plantwide.

Unlike most products on the market,

the intrinsically safe SCOUT devices

retain the same high performance

and long battery life as their non-rated COMMTEST brethren.

Ten hours of continuous use, while supporting up to: 80

kHz Fmax, 12,800 line spectral resolution, 6-Pack super fast

measurements, 4 channel simultaneous sampling, optional

tachometer. And the firmware updates automatically from

the handheld. Amazing!

Bently Nevada SCOUT200 series Powerful and connected

Powerful and connected

Vibration recordings are viewed and stored on the handheld

device. It runs the Android OS, so you can use it like any

smartphone or tablet to take pictures and video, send

text messages, check email, make phone calls, track your

location, create SOS alerts, and run other enterprise apps. Try

doing all that on an old school data collector!

High performance data acquisition

Unlike most products on the market,

the intrinsically safe SCOUT devices

retain the same high performance

and long battery life as their non-rated COMMTEST brethren.

Ten hours of continuous use, while supporting up to: 80

kHz Fmax, 12,800 line spectral resolution, 6-Pack super fast

measurements, 4 channel simultaneous sampling, optional

tachometer. And the firmware updates automatically from

the handheld. Amazing!

Bently Nevada SCOUT200 series Powerful and connected

Flexible handheld options

Choose from multiple handheld devices

to meet your form factor, screen size, and

hazardous rating needs. Update your

handheld at any time, load the System 1

Collector app onto the new device and get collecting.

So easy to carry

Carry the data acquisition module using a

shoulder strap or a belt clip. Sensors mount onto sensor

keepers. Hold the industrial smartphone or tablet in your

hand, on a belt clip, or on a neck strap. So you can focus on

your job and move safely between machines.

Powerful and connected

Vibration recordings are viewed and stored on the handheld

device. It runs the Android OS, so you can use it like any

smartphone or tablet to take pictures and video, send

text messages, check email, make phone calls, track your

location, create SOS alerts, and run other enterprise apps. Try

doing all that on an old school data collector!

Bently Nevada SCOUT200 series Portable vibration analyzers

Portable vibration analyzers

These portable data collector solutions record the vibration

of industrial machines, to monitor their condition and

diagnose their faults. The Series includes “SCOUT” models

for use in hazardous areas (explosive atmospheres) and

“COMMTEST” models for less stressful environments. There

are 2-channel and 4-channel versions of each, to suit your

data acquisition and analysis needs.

Designed in and for the 21st century

These two-part solutions utilize the power and

connectivity of modern industrial smartphones

and tablets, paired with a small form factor,

rugged data acquisition module. This gives the

best of both worlds, a fast handheld device full of accessories

and communication options, and a simple durable interface

to sensors on your machines.

CT/VT Modules with Enhanced Diagnostics Conclusion

Conclusion

CT/VT modules with enhanced diagnostics, released on 23 October 2006 with firmware 5.2.

offer much higher security for internal CT/VT module error detection and prevent undesired operations of URs.

Every UR firmware released since version 5.2 supports CT/VT modules with enhanced diagnostics,

which greatly improves the security and reliability of the protection system.

To take advantage of this feature, a relay hardware and possibly firmware upgrade is required.

If the existing relay has a firmware version below 4.0. GE recommends purchasing a

UR Upgrade Kit that allows modernization of the obsolete relay hardware

while taking advantage of the relay modularity.

The UR Upgrade Kit contains a new CPU and CT/VT modules that can be

inserted in an existing relay case (case is fully backwards compatible).

If the relay currently has firmware version 4.0 to 5.0. the latest firmware

can be downloaded from the GE Multilin website, and Enhanced Diagnostic

CT/VT modules (8L, 8M, 8N, 8R, 8S, 8V) can be purchased from the GE Online Store.

Consult with your local GE representative if you have any questions on the upgrade process.

CT/VT Modules with Enhanced Diagnostics Internal CT secondary monitoring

Internal CT secondary monitoring

The CT/VT input modules with enhanced diagnostics are monitoring internal CT circuitry integrity.

This is done to eliminate relay erroneous operation in case of CT secondary winding failure.

The secondary winding of CT is divided into two equal parts with a central tap in the middle.

CT current values from both halves of the CT secondary windings are run through

a differential amplifier to get a true current sample for the phasor calculations.

It also compares between each other by simply summing two samples together.

(Note that due to CT central tap, samples have different polarity.)

In case that values from different halves of the same CT accumulated over

one protection pass per adaptable per signal level do exceed the fixed error boundary,

failure is declared and protection is blocked.

CT secondary monitoring is performed at all four CT channels (A, B, C, and N) individually at each CT bank.

CT/VT Modules with Enhanced Diagnostics Analog data integrity validation

Analog data integrity validation

The CT/VT input modules (8L, 8M, 8N, 8R, 8S, 8V) use an analog data integrity

check to verify the performance of the analog measurement channels.

This feature uses an additional analog hardware channel that has as its input,

an analog sum of Sa = Xa – Xb + Xc + Xn, where X stands for either Voltage

or Current phases A, B, C, and N analog inputs, to monitor the integrity of analog data.

After the multiplexer samples analog channels via the sample and hold (S/H) mechanism,

 samples from all four channels are summed up digitally, using the same equation to get a digital value Sd.

The “Mean Square” of the difference between the channels is summed up

in the hardware and an equivalent, computed digitally over one protection

pass is supplied to the comparator. If the summed squared difference Σ(Sa – Sd)2

is greater than the adaptable per signal level error boundary,

then “invalid data” is declared and protection functions using the measured data are momentarily blocked.

In addition, if the error keeps repeating, a major self-test diagnostics error message is displayed on the UR.

As a result of such failure, the relay’s self-test alarm contact operates and the relay is taken out of service.

The relay can be rebooted and if no more failures are detected,

it continues to be functional unless a new failure is detected and the relay is again taken out of service.

The above analog data integrity check is performed on both analog banks

(that is, four currents or four voltages) within each CT/VT input module.

In addition, these modules with enhanced diagnostics include power supply

voltage rail monitoring to further monitor hardware health.

This is achieved by continuous check of the power supply voltage Vdc against

safe operate reference voltage Vref, which ensures that all electronic components

of the CT/VT module operate in the safe operating conditions.

CT/VT Modules with Enhanced Diagnostics INTRODUCTION

INTRODUCTION

The performance of a microprocessor-based relay is highly dependent

on the performance of the analog channels measurement of the relay,

as protection functions operate on these values.

The failure of an analog measurement channel, 

either due to a failure in the external measurement circuit,

or due to an internal failure inside a UR CT/VT module, 

can cause incorrect operation of protection functions.

The UR CT/VT modules with Enhanced Diagnostics (module types 8L, 8M, 8N, 8R, 8S, 8V)

can detect the failure of an analog channel measurement due to internal

failures of the CT/VT module, alarm for failure of the module,

and block tripping from any protection function associated with this module.

This feature is available when using firmware 5.20 or later within

the UR family and therefore field-proven since 2006.

ABB Power Supply SA 801F / SA 811F Technical Data

Technical Data SA 801F

Input voltage Alternating current 115 – 230 VAC

Permissible range 90 – 260 V AC

Frequency: 50 – 60 Hz (47 – 63 Hz)

Input current at

nominal load 230 V AC: 210 mA

115 V AC: 411 mA

Rated input power 48 VA

Backup energy for

the event of

power failure > 20 ms

Fuse Subminiature fuse 2.5 AT, soldered

Output voltage 3.3 V DC (± 3%) typical

5 V DC (± 3%) typical

Output current 0.5 – 5 A to 3.3V and 5.0 V

Current limit approx. 6 A

Automatic return to normal operation after

short circuit

Total output power max. 26.5 W

Weight 0.460 kg

Technical Data SA 811F

Input voltage Alternating current 115 – 230 VAC

Permissible range 90 – 260 V AC

Frequency: 50 – 60 Hz (47 – 63 Hz)

Input current at

nominal load 230 V AC: 275 mA

115 V AC: 541 mA

Rated input power 63 VA

Backup energy for

the event of power failure > 20 ms