Operation and configuration

LED indicator functions

The EAFR-101C contains 16 indication LEDs .  A user definable text

pocket can be slid in under the label for identifying each LED func

tion (except POWER and ERROR LEDs) .  LEDs are located at the

front plate of the relay for clear viewing without a need for opening

doors .

During power up, the relay performs an LED test .  All LEDs are

turned on for two seconds and then off .  Only the blue POWER LED

will remain on .  After powered up, the relay goes into protection

mode in 50 ms even while the LED test is being performed .

During normal operation, the blue power LED is ON, as are any CB

open/close status LED’s for connected CB’s .

The sensor LEDs are off during the inactive condition .  If  a point arc

sensor is activated, the corresponding sensor channel LED will turn

on if the activation is longer than 1 .5 ms .  The sensor LED activation

function is latched (steady light) .  To clear the LED, the “SET” button

should be pressed .

In case of a loose sensor wire and binary input wires or configura

tion mismatch (new sensor attached without running auto-configu

ration system setup (see Section 3 .3 .1) situation, the corresponding

LED for that sensor will start flashing and the ERROR LED will

activate .