Welcome to the official website of CNIACS Automation Technology Co., Ltd!

KEBA KeConnect DM 27x/A Digital hybrid modules


Digital inputs

DM 272/A DM 276/A

Number / wiring of inputs 8x sink 6x source

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Debouncing Configurable 1 ms, 100 ms

Cycle time 1 ms

Status display Green LED

Galvanic isolation Yes, electric strength 707 V with isolated ground connection

Interrupt inputs

Number of inputs Two of the digital inputs can be used as interrupt inputs

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Response time of the K-bus interrupt 50 μs

Status display Green LED

Galvanic isolation Yes

Digital outputs

DM 272/A DM 276/A

Number / wiring of outputs 8x source 8x sink

Nominal voltage 24 V DC

Processing time 1 ms

Nominal current of digital outputs 2 A at 50 % simultaneity

Protection facility Short-circuit protection

Max. inductive load 1 J at max 0.2 Hz

Status display Orange LED

Galvanic isolation Yes, from the control electronics and between one another,

electric strength 707 V with isolated ground connection

Dimensions, weight

Height 120 mm

Width 22.5 mm front plate / 32.5 mm incl. K-bus plug

Depth 100 mm

Weight 135 g

Environmental conditions

Operating temperature +5 °C … +55 °C

Storage temperature-40 °C … +70 °C

Relative air humidity 10 % to 95 % (non-condensing)

Vibration resistance / shock resistance Acc. to EN 61131-2

General

Supply voltage 24 V DC from front

(nominal voltage tolerance: 19.2 V to 30 V, acc. to EN 61131-2)

24 V DC from K-bus, 5 V DC from K-bus

Overvoltage category II

Protection class III acc. to EN 61131-2

Addressing on K-bus Via 16-digit address switch, on the side

Type of terminals Open – pitch 5.08 mm

Max. power consumption K-bus 24 V 1.9 W

Max. power consumption K-bus 5 V 0.4 W

KEBA KeConnect DM 27x/A Product features

Product features

• Up to 8 digital inputs

• 8 digital 2 A outputs

• 2 digital inputs with interrupt

• Short-circuit detection

• Permanently short-circuit proof

• Electronic rating plate

Short description

The DM 27x/A series is a digital input/output module of the KeConnect C2 product line and enables the

connection of 6 or 8 digital inputs and 8 digital outputs. 24 V DC control signals are captured by the

digital inputs and transmitted galvanically isolated to the higher-level automation device. In addition, two

of the digital inputs can be used as interrupt inputs.

The digital outputs switch the 24 V DC control signals of a CPU module galvanically isolated from the

connected actuators. In addition to the short-circuit connection, outputs that cause short circuits can be

switched off individually.

This module is attached directly to a CPU module or can be operated with all KEBA controls by means of a

bus coupler.

Digital inputs

DM 272/A DM 276/A

Number / wiring of inputs 8x sink 6x source

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Debouncing Configurable 1 ms, 100 ms

Cycle time 1 ms

Status display Green LED

Galvanic isolation Yes, electric strength 707 V with isolated ground connection

KEBA KeConnect DO 242/B, DO 272/A Digital output modules

Digital outputs

DO 242/B DO 272/A

Number of outputs 8 14

Nominal voltage 24 V DC

Processing time 1 ms

Nominal current of digital outputs 2 A at 50 % simultaneity

Galvanic isolation Yes

Status display Orange LED

Protection facility Short-circuit protection

Max. inductive load 1 J at max 0.2 HzC

Dimensions, weight

Height 120 mm

Width 22.5 mm front plate / 32.5 mm incl. plug

Depth 100 mm

Weight 130 g

Environmental conditions

Operating temperature +5 °C … +55 °C

Storage temperature-40 °C … +70 °C

Relative air humidity 10 % to 95 % (non-condensing)

Vibration resistance / shock resistance Acc. to EN 61131-2

General

DO 242/B DO 272/A

Supply voltage 24 V DC from front (nominal voltage tolerance: 19.2 V … 30 V, acc. to EN 61131-2)

24 V DC from K-bus, 5 V DC from K-bus

Overvoltage category II

Protection class III acc. to EN 61131-2

Addressing on K-bus Via 16-digit address switch, on the side

Type of terminals Open – pitch 5.08 mm

Displays on the front plate 16 signal status LEDs

Max. power consumption K-bus 24 V 2.1 W 2.1 W

Max. power consumption K-bus 5 V 0.4 W 0.4 W

KEBA KeConnect DO 242/B, DO 272/A Product features

Product features

• 8 or 14 digital outputs

• Short-circuit detection and diagnosis

• Permanently short-circuit proof

• Current load capacity 2 A at 50 % simultaneity

• Fast shutdown function for inductive loads

• Electronic parameter chip

Short description

Digital output modules DO 242/B and DO 272/A enable the connection of up to 14 digital outputs. The

digital outputs switch the 24 V DC control signals of a central module galvanically isolated from the

connected actuators and are designed for a load of up to 2 A at 50 % simultaneity.

The modules are equipped with a fast shutdown function that enables a rapid shutdown of inductive

loads, e.g., hydraulic valves. Machine processes can thereby be accelerated and productivity increased.

The operational safety is ensured by the permanent short-circuit protection of the outputs. Should a short

circuit occur, it is detected and reported to the control module.

These modules are attached directly to a CPU module or can be operated with all KEBA controls by means

of bus couplers.

KEBA KeConnect DI 240/B, DI 260/A Digital input modules

Interrupt inputs

Number of inputs 2 (DI0. DI1) of the digital inputs

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Response time of the K-bus interrupt 100 μs with 5 kHz input filter

Status display Green LED

Galvanic isolation Yes

Dimensions, weight

Height 120 mm

Width 22.5 mm front plate / 32.5 mm incl. K-bus plug

Depth 100 mm

Weight 130 g

Environmental conditions

Operating temperature +5 °C … +55 °C

Storage temperature-40 °C … +70 °C

Relative air humidity 10 % to 95 % (non-condensing)

Vibration resistance / shock resistance Acc. to EN 61131-2

General

I/O supply voltage 24 V DC from K-bus

5 V DC from K-bus

Overvoltage category II

Protection class III acc. to EN 61131-2

Addressing on K-bus Via 16-digit address switch, on the side

Type of terminals Open – pitch 5.08 mm

Max. power consumption K-bus 24 V 1 W

Max. power consumption K-bus 5 V 0.4 W

KEBA KeConnect DI 240/B, DI 260/A Product features

Product features

• Up to 16 digital inputs

• 2 digital inputs with interrupt

• Electronic parameter chip

• Configurable input filter

Short description

The digital input module of the DI 2xx/x series enables the connection of 8 (DI 240/B) or 16 (DI 260/A)

digital inputs.

24 V DC control signals are captured by the digital inputs and transmitted galvanically isolated to the

higher-level auto mation device. In addition, two digital inputs can be used as interrupt inputs.

These modules are attached directly to a CPU module or can be operated with all KEBA controls by means

of bus couplers.

Digital inputs

DI 240/B DI 260/A

Number of inputs 8 16

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Status display Green LED

Galvanic isolation Yes, electric strength 707 V with isolated ground connection

Cycle time 1 ms

Debouncing Configurable 1 ms, 100 ms

Interrupt inputs

Number of inputs 2 (DI0. DI1) of the digital inputs

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Response time of the K-bus interrupt 100 μs with 5 kHz input filter

Status display Green LED

Galvanic isolation Yes

Mersen Modulostar® CUS10 IEC+UL/CSA FUSE HOLDERS

FUSE HOLDERS, FUSE BASES AND SUPPORTS

IEC+UL/CSA FUSE HOLDERS

Mersen’s innovative Modulostar CUS10 fuse holders are finger-safe

under IEC standards to an IP20 grade of protection, including fuse

changing (with the flick of a finger). Modulostar CUS10 fuse holders

are available in 1. 2. 3 or 4 poles, with or without visual blown fuse

indicator, in UL + IEC version. Multi-pole units can also be field

assembled by ordering pin-ties assembly kit. Made of tough and

durable thermoplastic or thermoset material. For use with Mersen

midget fuses.

Mersen Modulostar® CUS10 IEC+UL/CSA FEATURES & BENEFITS

FEATURES & BENEFITS

•  Modular design

•  Compact design for space saving

•  DIN rail mounting

•  Degree of  protection: IP20

•  Finger safe

•  Easy access to the fuse

•  Lockable without accessory

•  Sealable in closed & open position

•  Optional visual blown fuse indicator

•  Multi-pole assembly kit available

•  Plastic material UL94V2 mini

•  Plastic material R22HL2 for railway application

•  Flame retardant materials with glow

wire flammability index to 960°C

•  Schock and vibration tested for

marine and railway applications

APPLICATIONS

•  All circuits up to 690V for protec

tion of motors, transformers, low

voltage distribution, control circuits,

drive protection

•  Non-load operation

STANDARDS

• UL Recognized Component,

UL4248. guide IZLT2

• CSA Component acceptance C22.2

• IEC 60269-2 and IEC 60947-3

• RoHS, Reach compliant

• Marine certificates

Mersen 690/700V Protistor® fuse-links provide maximum flexibility

The 690/700V Protistor® fuse-links provide maximum flexibility

in equipment design and ultimate protection for today’s power

conversion equipment. These aR ultra-fast acting square body

fuse-links are available in different body sizes, each size having

multiple worldwide acceptable mounting styles.

The Protistor® have been engineered to provide state-of-the-art

protection for semiconductors: diodes, thyristors and IGBT devices.

Fuses are assembled with die-cut elements embedded in solidified

sand, which helps control arcing characteristics for a lower I²t and

high interrupting rating level. All contact surfaces are silver plated

and all hardware is non-magnetic.

Each fuse-link can be equipped with a low voltage trip-indicator

which can operate a field mountable microswitch.

Mersen Protistor® size 32 aR 450 to 690VAC (IEC) / 700VAC (UL)

SEMICONDUCTOR PROTECTION FUSES

SQUARE BODY HIGH-SPEED FUSE-LINKS AC PROTECTION

FEATURES & BENEFITS

•  Multiple body sizes and terminals or blades combination

•  aR Class according to IEC 60269-4 and VDE 636-23

•  Very low I²t for improved semicon ductor protection

•  Ultra fast acting

•  Current limiting

•  Superior cycling capability

APPLICATIONS

•  Protection of inverters, motor

drives, UPS systems and similar

690V or less equipments.

STANDARDS

• IEC 60269-4 Compliance

• UL/CSA Recognized E76491 :

see « UL certified » status given in Product Range table

• CCC GB 13539.4 for Asian market only

The 690/700V Protistor® fuse-links provide maximum flexibility

in equipment design and ultimate protection for today’s power

conversion equipment. These aR ultra-fast acting square body

fuse-links are available in different body sizes, each size having

multiple worldwide acceptable mounting styles.

Search for products

Back to Top
Product has been added to your cart