Multilin™ M60 Under/Over Frequency Protection
Undercurrent Protection
The undercurrent protection element
provides the ability to trip the motor due
to external conditions that can cause the
load being pulled by the motor to drop
below a preset level. This element is useful
when the loss of the load results in a loss
of cooling which will cause the asset to
overheat.
Under/Over Frequency Protection
The under/over frequency protection
element detects when the motor is
operating at off-nominal frequencies
(which can damage the process) or signals
to upstream protection or control to
implement load-shedding actions.
RTD Protection (Module Option 5C)
The M60 RTD option provides 8
programmable RTD inputs per module that
are used for monitoring the stator, bearing
and ambient temperatures. Each RTD input
has 2 operational levels: alarm and trip. The
M60 supports RTD trip voting and provides
open RTD failure alarming. Alternatively,
a remote RTD module “RRTD”, which
supports 12 RTD inputs, can also be used
with the M60 for temperature monitoring.
The RRTD provides cost savings compared
with standard RTD wiring.