Voltage Drop Calculation Using American Wire Gauge
Example #1. one power supply per module (3x power supplies): A 18 AWG wire will drop 0.042 V/ft at 2.6
A at maximum ambient temperature. Using 100 feet between the QuickTrip and the power supply would
provide a voltage drop of 100×0.042 = 4.2V.
Example #2. one power supply for all three modules (1x power supply): A 18 AWG wire will drop 0.125
V/ft at 7.8 A at maximum ambient temperature. Using 100 feet between the QuickTrip and the power
supply would provide a voltage drop of 100×0.125 = 12.5V.
It is very important to ensure the voltage at the QuickTrip’s input terminal is within the product power
input specification to achieve maximum performance.
Extended Power Input
The Power Wiring Requirements section above specifies the maximum length of 30 meters between the
power source and the QuickTrip. Installations that require a longer power cable run also require a much
larger wire gauge to account for voltage drop. Figure 3-6 below gives a possible solution for installations
required to run at longer distances.