Control Input
The QuickTrip valves are controlled with the independent trip relay outputs from a trip system logic solver
such as the Woodward ProTechTPS.
Note: When used with the ProTechTPS, external power is not necessary for these inputs. All voltage
and isolation is provided within the ProTechTPS (24 VDC, 0.5 A).
Trip Points:
• If the input voltage drops below14 VDC, then the input will detect a Trip state.
• If the input voltage rises above 15 VDC, then the input will detect a Run state.
Control Input Isolation: 500 VAC from input to chassis.
Wiring Requirements
• Keep this and all other low level signal cables separated from input power cables to avoid
unnecessary coupling (noise) between them.
• Wire Gauge Range: 0.8 to 1.3 mm² / 16 to 28 AWG stranded wire.
• Shielding: The control inputs are unshielded; however, the wires should be kept in a twisted
configuration for noise immunity.
Position Feedback
There are two outputs for valve position feedback on each of the QuickTrip’s three valve modules (12
outputs total). Each of the two outputs features redundant connections. Both TRIP outputs and both RUN
outputs operate as normally open. The outputs can be wired to either switch load from positive supply or
switch load to ground. The user must supply the external 24 V supply for the output to function properly. If
using the Woodward ProTech TPS logic solver, the voltage may be supplied using the on-board discrete
power terminals (24 VDC, 0.050 A).