Manually Stroking QuickTrip (powered)

Manually Stroking Valve Procedure:

1. To manually stroke the QuickTrip valve, the actuators must be powered with 24 VDC. Make sure the

power supply is connected and operating while performing this procedure. This can be verified by

viewing the LED status through the sight window on top of the valve. One or two blue LED’s indicate

that the power supply is connected and is turned on.

2. If QuickTrip is in a run state, as indicated by a green LED as viewed through the sight glass,

QuickTrip may be manually tripped either by de-energizing the logic solver interposing relay to initiate

a trip state or by tripping the breaker to the Control In discrete input terminals on the QuickTrip

electronics module (terminals 5 and 6 of TB2).

3. If QuickTrip is in a trip state, as indicated by a red as LED viewed through the sight glass, QuickTrip

may be energized to close either by activating the logic solver interposing relay to initiate a run state

or by supplying a separate 24 VDC input to the Control In terminals on the QuickTrip electronics

module (terminals 5 and 6 of TB2).