Welcome to the official website of CNIACS Automation Technology Co., Ltd!

DEIF PPM 300 Highly customisable architecture

Highly customisable architecture

All PPM 300 variants can be specified with 4 or 7 I/O module slots. The modules provide

voltage and current measurement, I/O, engine control, governor and AVR functions,

and communication. Three modules are mandatory, but you can use the remaining 1

or 4 slots to customise the controller by adding modules or leave them empty.

In addition, you can add up to 9 expansion racks to a single PPM 300 to get up to 58

free module slots (up to 4 in the base rack and up to 6 in each expansion rack).

Unique ANSI 87G differential protection

With the optional ACM3.2 module, you can add ANSI 87G differential protection for generators.

The module measures phase currents on the consumer and neutral sides of a generator in order

to detect phase-to-phase faults or phase-to-earth faults in earthed generator systems.

With this unique feature, you can design reliable and safe power systems without external

differential protection devices.

DEIF PPM 300 Shaft generator controller

Customisable shaft generator controller designed for efficient power management

The PPM 300 Shaft generator controller controls and protects the system

when a shaft generator is connected, and it controls and protects the shaft generator breaker.

When a shaft generator is connected, it is normally the ship’s only power source,

but it can run in parallel with the gensets and supply a base load for an extended period

(long-time parallel). In such cases, the PPM 300 Shaft generator controller works with

the PPM 300 Genset controllers to ensure efficient power management.

A DEIF power management system can include as many Shaft generator controllers as necessary.

Part of the versatile PPM 300 range

The PPM 300 Shaft generator controller is part of the DEIF PPM 300 range of versatile

controllers with built-in multi-master power management features.

The range offers variants designed for a wide range of marine and offshore applications

–from generator control and protection to engineered power management solutions

developed for generators, battery energy storage, shore connections, and bus tie breakers.

For general information about the PPM 300 range, see the PPM 300 main page.

Highly customisable architecture

All PPM 300 variants can be specified with 4 or 7 I/O module slots. The modules provide

voltage and current measurement, I/O, engine control, governor and AVR functions,

and communication. Three modules are mandatory, but you can use the remaining 1

or 4 slots to customise the controller by adding modules or leave them empty.

In addition, you can add up to 9 expansion racks to a single PPM 300 to get up to 58

free module slots (up to 4 in the base rack and up to 6 in each expansion rack).

DEIF MVR-F205 Directional Feeder Protection

Features

Protection Functions:

• (Sensitive) Earth fault protection stages INST, DT or IDMT (ANSI 50N/51N(S))

• Auto-reclose (ANSI 79)

• Breaker failure protection (ANSI 50BF)

• Cable-end differential protection (ANSI 87)

• Cold-load pick-up block (ANSI 68)

• Current transformer supervision (ANSI 60L)

• Current unbalance/broken conductor protection stages INST, DT or IDMT (ANSI 46 /R/L)

• Directional (sensitive) residual over-current protection stages DT or IDMT (ANSI 67N)

• Directional three-phase over-current protection stages DT or IDMT (ANSI 67)

• Fault locator (ANSI 21FL)

• Frequency protection stages (ANSI 81O/U)

• Fuse failure (ANSI 60)

• Harmonic over-current protection/inrush blocking stages INST, DT or IDMT (ANSI 50H/51H/68)

• Overvoltage protection INST, DT or IDMT (ANSI 59)

• Positive/negative sequence under-/over-voltage protection INST, DT or IDMT (ANSI 27P/47/59P)

• Rate of Change of Frequency ROCOF (ANSI 81R)

• Residual voltage protection INST, DT or IDMT (ANSI 59N)

• Restricted low-impedance earth fault protection (ANSI 87N)

• Reverse-/under-/over-power protection INDT, DT or IDMT (ANSI 32)

• Switch onto fault logic (SOTF)

• Synchrocheck (ANSI 25)

• Thermal overload protection (line) (ANSI 49L)

• Three-phase over-current protection INST, DT or IDMT (ANSI 50/51)

• Under-voltage protection INST, DT or IDMT (ANSI 27)

• Voltage memory

DEIF MVR-F205 Directional Feeder Protection

The MVR-205 protection device comes with comprehensive measuring, monitoring and

communication features. Its standard configuration provides additional digital inputs and

outputs compared to the basic variant.

– 5x Current input (configurable 0.2…10A)

– 4x Voltage input (1.00…480.00V (RMS)

– 11x Digital input

– 10x Output relay (4NO, 1CO)

– 1x IRF output (1CO)

– 2x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)

– Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP 3.0. SPA protocols

– DT, IEC or ANSI time/overcurrent curves with settable release delays

Marine approvals:

– DNV/GL

– Lloyds Registeres LR

– Bureau Vertias BR

– ABS (USA)

– CCS (China)

– CNK (Japan)

– IEC (Israel)

– KR (Korea)

– UKCA (UK)

– RINA (Italy)

DEIF PPM 300 Features

PPM 300 features

► PMS with ring communication

► One touch sequences for genset start & stop, and breaker close & open

► Automatic synchronise and deload breaker

► Fast load reduction of less than 100 ms

► Advanced heavy consumer control

► Advanced fuel optimisation feature

► Advanced blackout prevention and recovery

► Broadcast of software

► Emulation and supervision

► High resolution 5″ colour graphic display with push-buttons

► Flexible and modular input/output with metal rack

► Plug & play, auto-configure I/O modules and network

► Integrated 5x RJ45 ports with auto-detected multi-function (e.g. display, PC Tool, Modbus TCP)

► All network controllers accessible through one Ethernet connection

► Context-sensitive help in the controller display unit

► Event and alarm log, with real-time clock

► Pre-defined control settings

► User-friendly logic configuration tool, based on ladder logic and function blocks with monitor

operation

► Password-protected, with customisable permission

► 3 phase AC measurement up to 690 V AC directly, class 0.5

► Easy-to-use PC tool (PICUS)

► Advanced alarm handling with latch and shelve functionality

► Network storm protected

DEIF PPM 300 Protection & power management

PPM 300 power management systems also incorporate market-leading fuel

optimisation technology as well as ABP, Advanced Blackout Prevention,

designed specially for Dynamic Positioning (DP) plants.

Being part of a multi-master solution, the integrated PPM 300 controllers connect

and communicate as a closed circuit to eradicate single point failures: in cases of

unit fall-out, the master functionality automatically moves to another host keeping

the system not just operational but safe and reliable at all times.

Built as a sturdy piece of market-leading quality hardware, the PPM 300 features

the latest processor technology and long-life adaptability.

Uniquely, the PPM 300’s modular build supports on-site replacement of processor,

communication, measurement and input-output modules with comprehensive class

approvals. Changes to the unit at sea or in the field are assisted with automatic

recognition functionality facilitating fast, easy and cost-saving service, repairs,

and upgrades. The controller display unit includes a 5” color graphic screen with

intuitive sequences and icons for fast readout of live data, and easy access to

alarms handling and controller setup. Functionality is defined and targeted

according to user permission levels.

DEIF PPM 300 solution is a versatile, intelligent generator control platform

Designed for applications in the marine and offshore industry, DEIF’s innovative

PPM 300 solution is a versatile, intelligent generator control platform.

Incorporating an extensive range of control, protection and supervision functions,

PPM 300 applications range from generator control and protection to engineered

power management solutions developed for diesel generators (including emergency

diesel generators), shaft generators, battery energy storage, shore connections,

and bus tie breakers. PPM 300 power management systems meet and maintain

set power requirements and guarantee stable operation.

PPM 300 power management systems also incorporate market-leading fuel

optimisation technology as well as ABP, Advanced Blackout Prevention,

designed specially for Dynamic Positioning (DP) plants.

DEIF The series of switch mode power supplies

The series of switch mode power supplies are compact, reliable and easy to install.

These power supplies are coated and designed for use in environment with bad

conditions like high humidity and high operating temperature. Marine approvals make

the power supplies suitable for applications at sea. For critical applications that require

absolute zero downtime DEIF also offer redundancy units at 10 and 20 A.

Features

• Power Boost function

• Low voltage detection output

• Side-by-side mounting

• Parallel operation

• Coated for protection against harsh environment

Power supply variants available at DEIF:

4.5 A

– Input: 100 to 240 V AC, 50/60 HZ, 90 to 350 V DC

– Output: 12 V DC, 4.5 A, 60 W

5 A

– Input: 85 to 264 V AC, 50/60 Hz, 90 to 350 V DC

– Output: 24 V DC, 5 A, 120 W

10 A

– Input: 85 to 264 V AC, 50/60 Hz, 90 to 350 V DC

– Output: 24 V DC, 10 A, 240 W

20 A

– Input: 85 to 264 V AC, 50/60 Hz, 90 to 350 V DC

– Output: 24 V DC, 20 A, 480 W

20 A (3ph)

–  Input: 380 to 480 V AC, 50/60 Hz, 450 to 600 V DC

– Output: 24 V DC, 20 A, 480 W

40 A (3ph)

– Input: 380 to 480 V AC, 50/60 Hz

– Output: 24 V DC, 40 A, 960 W

DEIF RMC-142D The relay measures the leakage

Measuring principle

The relay measures the leakage or a short circuit from one or more of the phases to earth.

In order to obtain a short response time on a fault condition, the measurement is based

on peak values.

The earth fault current protection is for example obtained by connecting an external current

transformer in the star point of the protected voltage source.

In order to prevent malfunction due to 3rd harmonic, the RMC-142D is equipped with

a special filter cutting off frequencies higher than 50/60 Hz.

The set point values are set on the front of the relay by means of potentiometers.

If exceeded, a fault signal is generated, and the associated yellow LED is lit.

Timer functions

When the set point is exceeded, its timer starts and will run as long as the fault condition prevails.

If the fault disappears, the timer is reset. When the timer expires, the contact is activated

and the associated red LED is lit.

Relay outputs

The RMC-142D is provided with two outputs with maximum contacts either normally

energised or normally de-energised.

The contact may be set to open or close on activation.

Normally energised contact

Recommended for warning and alarm purposes.

In case of an auxiliary supply dropout, the contact is immediately activated.

DEIF The RMC-142D is CE-marked and is applied for protection of voltage sources

Application

The protective stator earth fault relay type RMC-142D forms part of a complete

DEIF series of relays for protection and control of generators. The RMC-142D

is primarily designed for land-based installations. Also available are short circuit

relays (RMC-111D), combined short circuit and over-current relays (RMC-122D)

and double over-current relays (RMC-132D).

The RMC-142D is CE-marked and is applied for protection of voltage sources and

load networks against earth fault in a solid earthing or a low-resistance earthing system.

Normally de-energised contact

Recommended for installations for regulating and control purposes.

An auxiliary supply failure will not result in an unwanted activation of the contact.

Latch circuit

The contact can be locked in its warning position, even if the earth faulty current

(leakage current) returns to normal (add “L” to contact type in order specifications,

if this is required). The latch circuit is reset by disconnecting the auxiliary supply.

Hysteresis

In order to avoid “chatter” on the relay contacts the contact functions are provided

with a hysteresis, that is a difference of 2 % of full scale between energising and

de-energising of the delay.

Power-up/power-down circuits

The RMC-142D is provided with a 200 ms power-up circuit, ensuring the correct function

of the relay on connection of the auxiliary voltage.

Search for products