CTI 2559-RTD 8-Channel RTD Input Module
Specification
Input Channels: 8 independently configurable RTD input channels
RTD Type: 100 Ω Platinum: (TCR = 0.003850. Ω/Ω/oC) (European DIN43760 standard)
Temperature range: -198oC to 849.8oC (-327.6oF to 1561.6oF)
120Ω Nickel: (TCR = 0.00672. Ω/Ω/oC)
Temperature dcs-sis.com Range: -79.8oC to 260.0oC (-111.6oF to 500.0oF)
(Other RTD types on special request) 10Ω Copper
Absolute temperature accuracy: +0.4oC (+0.8oF)
Millivolt Range: 0 to 103.04 millivolts
Millivolt Input Impedance: >10KΩ @ 60Hz >10KΩ @ 60Hz >1000MΩ @ DC
Absolute millivolt accuracy +0.5% full scale or +500µV
Wire Compensation: 20Ω per wire
RTD probe bias current: 250 µA (nominal)
Digital filter time constant: 0.3 seconds
Output Units: Celsius or Fahrenheit (all outputs are jumper selectable)
Repeatability: 0.05% full scale
Resolution: 0.025% full scale
Update Time: 2 milliseconds per channel
Common mode rejection >110db @ 60Hz (digital filtering disabled)
Normal mode rejection >145db @ 60Hz (digital filter enabled)