ABB 1MDU07204-YNE Overview Feeder Protection REF601 Optional function

Optional function

Communication on MODBUS RTU Protocol

Other Functions

Self Supervision

The IED is provided with an extensive self-supervision system which

continuously supervises the software and the electronics.

It handles runtime fault situations and informs the user about an existing fault via the LHMI.

When in an IED internal fault is detected, the green Ready LED ceases to

glow and the self-supervision output contact is activated. Internal fault

indications have the highest priority on the LHMI. None of the other

LHMI indications can override the internal fault indication. An indication

about the fault is also shown as a message on the LHMI. The text IRF with

an additional text message, a code is shown to indicate the fault type.

The user can try to eliminate the fault by restarting the IED. If the fault is

still found, the IED stays in internal fault mode. All other output contacts

are released and locked for the internal fault.

The self-supervision signal output operates on the closed circuit principle.

Under normal conditions the relay is energized and the contact gap 5-6 in

connector XK2 is closed. If the auxiliary power supply fail or an internal

fault is detected, the contact gap 5-6 is opened.

ABB 1MDU07204-YNE Overview Feeder Protection REF601

Overview

REF601 is a dedicated feeder protection relay, intended for the protection

and control of utility substations and industrial power systems. 

The relay is compatible with the Rogowski coil sensor for current measurement. 

The feeder protection relay REF601 is designed to unleash the advantages of

current sensors for protection and control in medium voltage applications.

The REF601 features compact size and ease of use. 

The features include:

Sensor input for phase current measurement

Earth current measurement internally or externally through CBCT

Three-stage overcurrent protection

Two-stage earth-fault protection

Inrush detection for stability during transformer charging

Local and remote control of circuit breaker

Trip Circuit Supervision

Lockout function

100 event logs

Two analogue fault records

Non-resettable trip counter

On-line current measurements in primary value

Comprehensive local HMI

Universal auxiliary supply

Compact design suitable for circuit breaker or panel mounting

Optional MODBUS RTU communication

Non-volatile memory for setting and fault records

Self-supervision

User selectable rated frequency 50 / 60 Hz

Operation Functionality

Relay functions

REF601 offers pre-configured functionality which facilitates easy and fast

commissioning of switchgear. To emphasize the relay’s simplicity of usage,

only application specific parameters needs to set within the relay’s intended area of application.

The settings can be changed by LHMI (local human-machin interface) or

through optional communication interface MODBUS master with setting capability.

The relay offers protection, control, measurement and condition monitoring functionality.

ABB 1MDU07204-YNE General Feeder Protection REF601 Intended audience

Intended audience

This manual addresses system engineers, installation and commissioning

personnel, who use technical data during engineering, installation and

commissioning, and in normal service. system engineer must have a

thorough knowledge of protection systems, protection equipment,

protection functions and the configured functional logics in the IEDs.

The installation and commissioning personnel must have a basic

knowledge in handling electronic equipment.

This manual addresses Protection and control engineer responsible for

planning, pre-engineering and engineering. The protection and control

engineer must be experienced in electrical power engineering and have

knowledge of related technology, such as communication and protocols.

The manual also addresses the operator, who operates the IED on a daily

basis. The operator must be trained in and have a basic knowledge of

how to operate protection equipment. The manual contains terms and

expressions commonly used to describe this kind of equipment.

ABB 1MDU07204-YNE General Feeder Protection REF601

General

This manual

This manual contains application and functionality descriptions and

connection diagrams, input and output signals, setting parameters and

technical data. The manual can be used as a technical reference during

the engineering phase, installation and commissioning phase, and during

normal service. The manual can also be used when calculating settings.

Instructions on how to operate the IED during normal service once it has

been commissioned and it can be used to find out how to handle

disturbances or how to view calculated and measured network data in

order to determine the cause of a fault.

ABB 1MRK505137-BEN Hardware description Line differential protection IED RED670 LDCM

communication module (SLM)

The optical serial channel and LON channel module is used to connect an IED to the communication that use SPA,

 LON, or IEC60870–5–103. 

The module has two optical ports for plastic/plastic, plastic/glass, or glass/glass.

Line data communication module (LDCM)

The line data communication module is used for binary signal transfer. 

Each module has one optical port, one for each remote end to which the IED communicates.

Alternative cards for Long range (1550 nm single mode), Medium range (1310 nm single mode) and

Short range (900 nm multi mode) are available.

GPS time synchronization module (GSM)

This module includes the GPS receiver used for time synchronization. 

The GPS has one SMA contact for connection to an antenna.

Transformer input module (TRM)

The transformer input module is used to galvanically separate and transform the secondary currents and voltages generated by the measuring transformers. 

The module has twelve inputs in different combinations.

High impedance resistor unit

The high impedance resistor unit, with resistors for pick-up value setting and a voltage dependent

resistor, is available in a single phase unit and a three phase unit. 

Both are mounted on a 1/1 19 inch apparatus plate with compression type termnals.

ABB 1MRK505137-BEN Hardware description Line differential protection IED RED670 IOM

Binary input/output module (IOM)

The binary input/output module is used when only a few input and output channels are needed. 

The ten standard output channels are used for trip output or any signalling purpose. 

The two high speed signal output channels are used for applications where short operating time is essential. 

Eight optically isolated binary inputs cater for required binary input information.

mA input module (MIM)

The milli-ampere input module is used to interface transducer signals in the –20 to +20 mA range

from for example OLTC position, temperature or pressure transducers.

The module has six independent, galvanically separated channels.

Optical ethernet module (OEM)

The optical fast-ethernet module is used to connectan IED to the communication buses 

(like the station bus) that use the IEC 61850-8-1 protocol. 

The module has one or two optical ports with ST connectors.

Serial SPA/IEC 60870-5-103 and LON

ABB 1MRK505137-BEN Hardware description Line differential protection IED RED670

Hardware modules

Power supply module (PSM)

The power supply module is used to provide the correct internal voltages and full isolation between the terminal and the battery system. 

An internal fail alarm output is available.

Binary input module (BIM)

The binary input module has 16 optically isolated inputs and is available in two versions, 

one standard and one with enhanced pulse counting capabilities on the inputs to be used with the pulse counter function. 

The binary inputs are freely programmable and can be used for the input of logical signals to any of the functions.

They can also be included in the disturbance recording and event-recording functions. 

This enables extensive monitoring and evaluation of operation of the IED and for all associated electrical circuits.

Binary output modules (BOM)

The binary output module has 24 independent output relays and is used for trip output or any signal ling purpose.

ABB 1MRK505137-BEN Line differential protection IED RED670 Application 2

The auto-reclose for single-, two- and/or three phase reclosing includes priority circuits for multi-breaker arrangements. 

It co-operates with the synchrocheck function with high-speed or delayed reclosing.

High set instantaneous phase and earth overcurrent, four step directional or un-directional delayed phase and earth overcurrent,

thermal overload and two step under and overvoltage functions are examples of the available functions allowing the

user to fulfill any application requirement.

The IED can also be provided with a full control and interlocking functionality including co-operation 

with the synchrocheck function to allow integration of the main or back-up control.

The advanced logic capability, where the user logic is prepared with a graphical tool, 

allows special applications such as automatic opening of disconnectors in multi-breaker arrangements, closingof breaker rings, load transfer logics etc. 

The graphical configuration tool ensures simple and fast testing and commissioning.

Serial data communication is via optical connections to ensure immunity against disturbances.

The wide application flexibility makes this product an excellent choice for both new installations and the refurbishment of existing installations.

ABB 1MRK505137-BEN Application Line differential protection IED RED670

Application

The RED 670 IED is used for the protection, control and monitoring of overhead lines and cables in all types of networks. 

The IED can be used up to the highest voltage levels. 

It is suitable for the protection of heavily loaded lines and multi-terminal lines where the requirement for tripping is one-,two-, and/or three pole. 

The IED is also suitable for protection of cable feeders to generator block transformers.

The phase segregated current differential protection provides an excellent sensitivity for high resistive faults and gives a secure phase selection.

The availability of six stabilized current inputs allows use on multi-breaker arrangements in three

terminal applications or up to five terminal applications with single breaker arrangements.

Remote communication based on the IEEE C37.94 standard can be redundant when required for important installations. 

Charging current compensation allows high sensitivity also on long overhead lines and cables.

A full scheme distance protection is included as independent protection or as back-up at remote end communication failures. 

Eight channels for intertrip and binary signals are available in the communication between the IEDs.

ABB 1MRK505137-BEN Monitoring Line differential protection IED RED670

• Logic

– Tripping logic (PTRC, 94)

– Trip matrix logic

– Configurable logic blocks

– Fixed signal function block

• Monitoring

– Measurements (MMXU)

– Supervision of mA input signals (MVGGIO)

– Event counter (GGIO)

– Event function

– Disturbance report (RBDR)

– Fault locator (RFLO)

• Metering

– Pulse counter logic (GGIO)

• Station communication

– IEC61850-8-1 communication

– LON communication protocol

– SPA communication protocol

– IEC 60870-5-103 communication protocol

– Horizontal communication via GOOSE for interlocking

– Single command, 16 signals

– Multiple Command, 80 blocks with 16 signals each

– Ethernet configuration of links

• Remote communication

– Binary signal transfer

• Basic IED functions

– Self supervision with internal event list

– Time synchronization (TIME)

– Parameter setting groups

– Test mode functionality (TEST)

– Change lock function

– IED identifiers

– Rated system frequency

• Hardware

– Power supply module (PSM)

– Binary input module (BIM)

– Binary output module (BOM)

– Binary in/out module (IOM)

– mA input module (MIM)

– Transformer input module, standard compression connection terminals (TRM)

– Optical ethernet module (OEM)

– SPA/LON/IEC module (SLM)

– Line data communication module (LDCM)

– GPS time synchronization module (GSM)

• Accessories

– GPS antenna, including mounting kit

– External interface converter from C37.94 to  G703

– High impedance resistor unit

– Test switch module RTXP24

– On/off switch

Search for products

Back to Top
Product has been added to your cart