REX640 includes two autoreclosing functions, each with up to
five programmable autoreclosing shots of desired type and
duration. A load-shedding function performs load shedding
based on underfrequency and the rate of change of the
frequency.
To validate correct closing conditions for a circuit breaker,
REX640 contains a synchrocheck function. For installations
including synchronous generators, REX640 introduces a
synchronizer that actively controls the generator’s voltage and
frequency in order to reach a synchronous situation across the
circuit breaker. The synchronizer functionality is available for a
generator circuit breaker as well as for a non-generator
(network) circuit breaker. A complete installation-wide
synchronizing system can be built using the REX640 relays. The
maximum size of the synchronizing system is eight generator
breakers and 17 non-generator breakers.
Synchronization of a generator circuit breaker can be
implemented using a single REX640 relay including the
ASGCSYN function block. The relay interfaces the external
measurement and control circuitry via hardwired binary and
analog signals. The excitation and prime mover control signals
are based on pulse commands, either with fixed or variable
length. The synchronizer function block has three different
function modes: manual, semi-automatic and automatic. In
each of these modes, the LHMI acts as the local user interface.
The LHMI includes the necessary command, indication and
measurement features for each of the modes, thus rendering
the conventional dedicated synchronizing panel unnecessary.
REX640 also supports systems in which non-generator circuit
breakers are synchronized. The prerequisite is that all the
feeders within the system are equipped with REX640 relays.