The LHMI includes the necessary command, indication and

measurement features for each of the modes, thus rendering

the conventional dedicated synchronizing panel unnecessary.

REX640 also supports systems in which non-generator circuit

breakers are synchronized. The prerequisite is that all the

feeders within the system are equipped with REX640 relays.

The generator relays have to contain the ASGCSYN function

block and all the non-generator relays need to contain the

ASNSCSYN function block. In addition, all the REX640 relays

have to contain the coordinator function block ASCGAPC. The

role of ASCGAPC is to model the system primary circuit

connection state to involve the correct generators for the

synchronization of a non-generator breaker and to interact

between the ASGCSYN and ASNSCSYN function blocks. The

information exchange between ASCGAPC, ASGCSYN and

ASNSCSYN is carried out via binary and analog GOOSE

signalling as per IEC 61850-8-1. The LHMI dedicated to the

relay (breaker) works as the local user interface for a non

generator breaker synchronizing. The available synchronizing

modes are “automatic” and “semi-automatic”. A manual

synchronization of the non-generator breaker can be carried

out as a back-up solution in situations where the

communication system (IEC 61850-8-1) is not available. This

requires operator actions from two LHMIs, namely from the

LHMI of the concerned non-generator breaker and the LHMI of

the manually selected generator relay.