Analog inputs

• Three phase currents: 5/1 A programmable

• Ground current: 5/1 A programmable or 0.2 A

Rated frequency: 60/50 Hz programmable

• Three-phase and ground voltages: programmable

nominal secondary voltage (available as options)

Binary inputs and outputs

• Four, eight with VT inputs, binary inputs standard

• Two NO outputs with trip circuit monitoring

• Three NO outputs

• One Form C output and self-check alarm output

• Additional binary inputs and outputs available as options

Communication

• IEC 61850-8-1 with GOOSE messaging

• DNP3.0 Level 2+ over TCP/IP

• Modbus over TCP/IP

• Time synchronization via SNTP (primary and backup servers)

• Optional serial RS-485 port programmable for

DNP3.0 Level 2+ or Modbus RTU

• Optional IRIG-B time synchronization

• Optional HSR/PRP communication

• Optional IEEE1588v2 time synchronization (available

with REF615 V5.0 and later)

• IEC61850-9-2LE (available with REF615 V5.0 and later)

Product dimensions and weights

• Frame: 6.97” (177 mm) W x 6.97” (177 mm) H

• Case: 6.57” (165 mm) W x 6.30” (160 mm) H x 6.10”

(155 mm)

• Weight: Relay – 7.72 lbs. (3.5 kg); Draw-out unit – 3.97

lbs. (1.8 kg)

Tools

• PCM600 V2.8 for setting, configuration and data retrieval

• COM600 Station Automation series products V5.0

• Web browser based user interface (IE 11 or later)

Certificates

• UL Listed product, File E103204

Control voltage

• Option 1: 48 … 250 V dc, 100 … 240 V ac

• Option 2: 24 … 60 V dc