Bus protection via GOOSE

The IEC 61850 implementation in PCMU MSOC includes

fast peer-to-peer communication, over the substation bus.

Use GOOSE communication between PCMU MSOC relays of

the incoming and outgoing feeders of a substation to form a

stable, reliable, and high-speed busbar protection system. The

cost-effective GOOSE-based busbar protection is obtained by

configuring the relays and the operational availability of the pro

tection is assured by continuous supervision of the protection

devices and their GOOSE messaging over the station bus. No

separate hard-wiring is needed for the horizontal communica