Bus protection via GOOSE
The IEC 61850 implementation in PCMU MSOC includes
fast peer-to-peer communication, over the substation bus.
Use GOOSE communication between PCMU MSOC relays of
the incoming and outgoing feeders of a substation to form a
stable, reliable, and high-speed busbar protection system. The
cost-effective GOOSE-based busbar protection is obtained by
configuring the relays and the operational availability of the pro
tection is assured by continuous supervision of the protection
devices and their GOOSE messaging over the station bus. No
separate hard-wiring is needed for the horizontal communica
tion between the switchgear cubicles.