Pre-emptive condition monitoring
For continuous knowledge of the operational availability of the
PCMU MSOC features, a comprehensive set of monitoring
functions to supervise the relay health, the trip circuit, and the
circuit breaker health is included. The breaker monitoring can
include checking the wear and tear of the circuit breaker, the
spring charging time of the breaker operating mechanism and
the gas pressure of the breaker chambers. The relay also mo
nitors the breaker travel time and the number of circuit breaker
operations to provide basic information for scheduling breaker
maintenance.
Bus protection via GOOSE
The IEC 61850 implementation in PCMU MSOC includes
fast peer-to-peer communication, over the substation bus.
Use GOOSE communication between PCMU MSOC relays of
the incoming and outgoing feeders of a substation to form a
stable, reliable, and high-speed busbar protection system. The
cost-effective GOOSE-based busbar protection is obtained by
configuring the relays and the operational availability of the pro
tection is assured by continuous supervision of the protection
devices and their GOOSE messaging over the station bus. No
separate hard-wiring is needed for the horizontal communica
tion between the switchgear cubicles.