The LHMI includes the necessary command, indication and
measurement features for each of the modes, thus rendering
the conventional dedicated synchronizing panel unnecessary.
REX640 also supports systems in which non-generator circuit
breakers are synchronized. The prerequisite is that all the
feeders within the system are equipped with REX640 relays.
The generator relays have to contain the ASGCSYN function
block and all the non-generator relays need to contain the
ASNSCSYN function block. In addition, all the REX640 relays
have to contain the coordinator function block ASCGAPC. The
role of ASCGAPC is to model the system primary circuit
connection state to involve the correct generators for the
synchronization of a non-generator breaker and to interact
between the ASGCSYN and ASNSCSYN function blocks. The
information exchange between ASCGAPC, ASGCSYN and
ASNSCSYN is carried out via binary and analog GOOSE
signalling as per IEC 61850-8-1. The LHMI dedicated to the
relay (breaker) works as the local user interface for a non
generator breaker synchronizing. The available synchronizing
modes are “automatic” and “semi-automatic”. A manual
synchronization of the non-generator breaker can be carried
out as a back-up solution in situations where the
communication system (IEC 61850-8-1) is not available. This
requires operator actions from two LHMIs, namely from the
LHMI of the concerned non-generator breaker and the LHMI of
the manually selected generator relay.