Chemically Resistant Versions
For steam turbine applications where lube oil contains harsh chemical contaminants (ammonia, hydrogen
sulfide, etc.), a chemically resistant version of the QuickTrip has been developed. Chemically resistant
versions feature best-in-class seals in all wetted locations within the trip block assembly. Chemically
resistant versions provide an optimal solution for extreme chemical resistance while still maintaining
QuickTrip operating pressure and temperature ranges. Please contact Woodward for available models
and information regarding chemical resistance for specific applications.
Rotary Trip Valves
All three of the QuickTrip’s trip valves are spring return, two position rotary valves. When any of the
hydraulic valves is in its closed position, the ports in the valve are blocked preventing hydraulic flow
through the valve. As a valve rotates to the tripped position, the ports open and the trip header pressure
is connected to either the drain, or the inlet ports of another one of the valves. The combined action of the
three valves results in trip header pressure being connected to drain only when 2 or 3 valves are tripped.
If the unit detects any shutdown condition or loss of power occurs, the trip valve return springs will force
the valves to the fail-safe / tripped position.