Fuel Flow
Gas fuel flow is normally achieved by the accurate scheduling of the metering valve port area, based on
values for gas properties, operating pressures, and temperature. The GS-Series valve is factory calibrated
under flow and pressure conditions to provide an accurate valve metering to the input demand signal.
Flow equations for the valves are located in the O&M manual. These can be used to set up the valve for
any site-specific conditions.
Port Sizes
The GS-Series is available with five different port sizes to optimize valve performance for various flow and
pressure drop requirements. Standard port effective area sizes are:
GS40
• 0.30 in² (193.5 mm²)
• 0.75 in² (483.9 mm²)
GS50
• 1.0 in² (645.2 mm²)
• 1.5 in² (967.7 mm²)
• 2.0 in² (1290.3 mm²)
The standard metering ports are contoured to provide approximately square law relationships between
commanded position and effective area.