MSLC functions include:
Selectable for phase matching or slip frequency synchronizing between the
utility and a local bus with voltage matching;
Automatic system loading and unloading for bumpless load transfer;
Import/Export level control capability;
Process control for cogeneration, pressure, maintenance, or other process;
Proportional loading of associated DSLC controls in isochronous load sharing;
Adjustable Power Factor control;
Built in diagnostics with alarm relay driver output;
Multi-function adjustable high and low limit alarms and adjustable load
switches with relay driver outputs;
Digital communications network to provide loading and power factor control
of individual DSLC equipped generators;
Full setup, metering, and diagnostic capability through a hand held
programmer terminal (Figure 1-2).