The CHARM I/O card (CIOC) connects through the controller’s redundant Ethernet

ports to provide a highly distributed and flexible I/O solution called an e-solution.

solution. Up to 16 CIOCs can be connected to a single controller,

each providing up to 96 individually controllable signal types.

SQ controller capacity limits may vary depending on the specific application,

number of CHARM I/O signals, and control performance requirements.

Enhanced Memory Handling and Hardware Alarms, Indexed to Cover Capacity and Memory

Enhanced memory handling and hardware alarms covering capacity and memory

have been added to the SQ controller’s diagnostic information through indexing.

The WirelessHART I/O Card (WIOC) provides redundant communications

for up to 100 WirelessHART devices, ensuring high availability and reliability of wireless data.

Up to 16 WirelessHART I/O cards can be connected to a single controller, each providing up to 100

signals.

The controller automatically schedules control modules based on the assigned scan rate.

This allows each control function to be dynamically optimized for the process.

Module scan times can be set as fast as 100 milliseconds and as slow as 60 seconds.

The number of control modules that can be assigned to the controller depends

on the complexity and scan rate of each module, as well as the available CPU and memory.

The SQ controller is suitable for small to medium sized applications with up to 750 independent I/O

signals.