Electrical life
The electrical life of V-Contact VSC contactors is defined in category AC3.
Interruption principle
The main contacts operate inside the vacuum interrupters (the level of
vacuum is extremely high: 13 x 10 -5 Pa).
On opening, there is rapid separation of the fixed and moving contacts in each contactor interrupter.
Overheating of the contacts, generated at the moment they separate,
causes formation of metallic vapours which allow the electric arc
to be sustained up to the first passage through zero current.
On passage of zero current, cooling of the metallic vapours allows
recovery of high dielectric resistance able to withstand high values
of the return voltage.
For motor switching, the value of the chopped current is less than
0.5 A with extremely limited overvoltages.