Protection and Features:
• Electronic thermal motor protection against overload.
• Temperature monitoring of the heatsink ensures that the frequency converter trips in case of
overtemperature
• The frequency converter is protected against short-circuits between motor terminals U, V, W.
• If a motor phase is missing, the frequency trips and issues an alarm.
• If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
• Monitoring of the intermediate circuit voltage ensures that the frequency converter
trips if the intermediate circuit voltage is too low or too high.
• The frequency converter is protected against earth faults on motor terminals U, V, W
The cooling capability of air is decreased at low air pressure.
For altitudes above 2000 m, please contact GE .
Below 1000 m altitude no de-rating is necessary but above 1000 m the ambient
temperature or the maximum output current should be decreased.
Decrease the output by 1% per 100 m altitude above 1000 m or reduce the max.
ambient temperature by 1 degree per 200 m