MONITOR FUNCTIONS
SYSTEM POWER-UP INHIBIT
The System Monitor provides a Power-up Inhibit function. This function allows each monitor to
inhibit its alarms during power-up or whenever a system supply voltage falls below its operating
level. After power-up, the inhibit function remains active for approximately 2 seconds.
RACK INHIBIT
When activated by a external contact closure this function places all monitors in bypass, disables
all alarms, zero scales all outputs, and de-energizes the system OK relay. The connections for this
function are located on the power input module (PIM) at the rear of the rack.
SUPPLY VOLTAGES OK
Seven LEDs located behind the front panel of the System Monitor are ON to indicate the voltage
supplies are functioning. The voltage supplies are +VRH, +VRL, +7.5V, +5V, REF, -7.5V, and -VT.
There is a green LED (SUPPLIES OK) on the front panel of the System Monitor. When this LED is on
all of the voltage supplies are functional.
SYSTEM RESET
The System Monitor provides the ability to cause a System Reset. Closing external contacts
through terminals on the PIM or pressing the RESET switch on the front panel will cause a System
Reset.