System Operation
Tle power
• Module operation
• Error (module error and channel error)
Cycle Power
When you cycle the module’s power, the RTD module checks its
internal circuits, memory, and basic functions via hardware and
software diagnostics. During this time the module status LED indicator
remains off. If no faults are found during the diagnostics, the module
status LED indicator is on.
After the checks are complete, the RTD module waits for valid
channel configuration data from your SLC ladder logic program
(channel status LED indicators off). After configuration data is written
to one or more channel configuration words and their channel enable
bits are set by the user program, the channel status LED indicators go
on and the module continuously converts the RTD or resistance input
to a value within the range you selected for the enabled channels. The
module is now operating in its normal state.
Each time a channel is read by the module, that data value is tested by
the module for a fault condition, for example, open circuit, short
circuit, over range, and under range. If such a condition is detected, a
unique bit is set in the channel status word and the channel status
LED indicator blinks, indicating a channel error condition.