Auto Reset Operation

IMPORTANT

1746-HSCE2 outputs perform auto-reset under overload 

conditions. When an output channel overload occurs as 

described above, all channels turn off within milliseconds 

after the thermal cut-out temperature has been reached. While 

the overcurrent condition is present, the module tries resetting 

the outputs at intervals of 500 ms. If the fuse cools below the 

thermal cut-out temperature, all outputs will auto-reset and 

resume control of their external loads as directed by the 

module until the thermal cut-out temperature is again reached.

Removing power from an overloaded output channel would 

also allow the fuse to cool below the thermal cut-out 

temperature, allowing auto-reset to occur when power is 

restored. The output channel then operates as directed by the 

module until the thermal cut-out temperature is again reached.

To avoid auto-reset of output channels under overload 

conditions, monitor the fuse blown status bit (FB1) in the 

module’s status file and latch the output off when an 

overcurrent condition occurs. An external mechanical fuse 

can also be used to open an output circuit when it is overloaded.