Output File
contains 32 16-bit entries used by ladder program to command
module operation. The Output File may also be used to supply
process data to the module in certain situations. Entries in this
file are updated automatically, at the end of each scan, by the
SLC processor from the user data file but may be written at any
time by immediate I/O instructions in the ladder program.
Input File
contains 32 16-bit entries used by ladder program to extract
status information from the module. The Input File contains
acknowledge bits corresponding to control bits in the Output
File, as well as information pertaining to the profile executing on
each analog I/O channel (step number, setpoint, analog input,
process variable, control output, etc.) and a parameter error flag.
The entries in this file are read automatically, once per scan, by
the SLC processor into the user data file, but may be read at any
time by immediate I/O instructions in ladder program.