Application
The REF601 and REJ601 are protection relays aimed at protection and control of incoming and outgoing feeders in MV distribution substations.
They can be applied for short-circuit, overcurrent and ground-fault protection of
overhead lines and cable feeders of distribution and sub-distribution networks.
The inrush current stabilization function allows the relays to be
used as the main protection for distribution transformers.
The relay with application configuration B offers non-directional
overcurrent and ground-fault protection. The residual current for
the ground-fault protection is derived from the phase currents.
When applicable, core-balance current transformers can be
used for measuring the residual current, especially when sensitive ground-fault protection is required.
The application configuration C adds thermal overload protection for feeders, cables and transformers, phase discontinuity
protection and circuit breaker failure protection.
The application configuration D provides the highest functionality with incorporation of negative
phase sequence protection and a multi-shot auto-recloser function making the relay suitable for overhead line feeders.