SPECIFICATIONS

Power Supply

Operating Voltage

(Reverse polarity protected)

8.0 VDC to 35.0 VDC, Continuous Power

Supply.

Maximum supply voltage Short Time 80 V (5-10 s); Long T. 50 V

Minimum supply voltage 6.5 V

Maximum operating current (All relays closed, LCD bright)

380 mA (12 V); 188 mA (24 V)

Maximum standby current (All relays closed, LCD dimm)

90 mA (12 V); 42 mA (24 V)

Power Consumption <4 W (standby ≤ 2 W)

Battery voltage measurement  Accuracy: 1% (12V/24V)

Alternator Input Range

3-Phase 4-Wire

3-Phase 3-Wire

Single-Phase 2-Wire

2-Phase 3-Wire

50 Hz/60 Hz

AC15V – AC360V (ph-N)

AC30V – AC620V (ph-ph)

AC15V – AC360V (ph-N)

AC15V – AC360V (ph-N)

AC-Measurement

Voltage Accuracy

(400/480 V % rated)

Phase-phase: 100 .. 624 V:1%;

50 .. 100 V:1.5 %

Phase-neutral: 100 .. 360 V:1%

50 .. 100 V:1.5 %

Minimum frequency Generator: 10 Hz; Mains: 27 Hz

Maximum frequency Generator: 99.5 Hz; Mains: 99.5 Hz

Frequency resolution 0.1 Hz (10 .. 99 Hz)

Frequency accuracy ±0.1 Hz

Nominal CT secondary rating 5 A

Overload Measurement Max.: 10 A

Current Accuracy 1 %

Housing

Case Dimension easYgen-600: 209 X 166 x 45 mm3

easYgen-800: 237 x 172 x 45 mm3

Panel Cutout easYgen-600: 186 x 141 mm2

easYgen-800: 214 x 160 mm2

Working Conditions Temperature: (-25 to +70) °C;

Humidity: (20 to 93) %RH

Storage Condition Temperature: (-25 to +70) °C

Protection Level IP65 in the front, mounted with kit

IP20 on rear side