Power Utilities
• Middle of the road solution for medium-criticality transformers
• Monitoring together with remote exploratory diagnostic
Industrial Plants
• Reduces the risk of process interruption due to power failure
• Minimizes costly production downtime
All types of incipient faults are covered by the monitoring of hydrogen gas levels. Slowly eroding
paper faults can be exposed through the monitoring of carbon monoxide. Various degrees of thermal
faults, including arcing, can be detected and identified, often leading to a transformer repair rather
then a much more costly transformer rebuild.
In particular, the TRANSFIX DGA 500 enables the well known Duval’s triangle DGA diagnostic
described in Appendix B of IEC Standard 60599. It uses the value of 3 gases (Acetylene, Ethylene and
Methane) and is suitable for identifying various degrees/temperature of thermal faults as well as the
presence of high-energy electrical discharge faults.