RX3i Universal Backplane Installation
The RX3i system and its components are considered open equipment (having live electrical parts that may
be accessible to users) and must be installed in a protective enclosure or incorporated into other
assemblies manufactured to provide safety. As a minimum, the enclosure or assemblies must provide
protection equivalent to a NEMA/UL Type 1 enclosure or an IP20 rating (IEC60529). The enclosure must
be able to adequately dissipate theheat generated by all of the components mounted inside so that no
components overheat. A minimum space of at least 102mm (4 inches) as shown below is required on all
sides of the RX3i backplane for cooling. Additional space may be required, depending on the amount of
heat generated by the equipment during operation.
Please refer to the PACSystems RX3i System Manual, GFK-2314. for information about enclosures and
heat dissipation.
Backplane Orientation
Backplanes must be mounted horizontally to meet product
performance and reliability specifications by providing
adequate airflow around the modules. Other mounting
orientations may affect system performance and/or reliability
and are therefore not recommended.