SPECIFICATIONS
Supported sensors
Currently available :Compatible with a range of sensors and signal conditioners using
2-wire current transmission and 3-wire voltage transmission
Dynamic input channels
Number of independent channels : 2
Measurement range
•Voltage (AC+DC) : ± 3 or ± 30 VPEAK
•Current : 15 or 150 mA
Frequency bandwidth (−0.1 dB) : 0.1 Hz to 19 kHz
•Analog high-pass filter :An optional (software configurable) analog high-pass filter can be
added to the AC path to configure the high-pass cutoff frequency
(−3 dB) as 0.1. 1.0 or 3.0 Hz.
This filter can also be disabled to allow DC-coupling of the input.
Input impedance
•Voltage : ≥ 100 kΩ, between the differential (high and low) inputs
•Current : 202 Ω ± 3 Ω, between the differential (high and low) inputs
Accuracy
•Amplitude : ≤ 1% of input FSD (measurement bandwidth from 10 Hz to 1 kHz)
•Phase : ≤ 1.5 ° (measurement bandwidth from 10 Hz to 1 kHz)
Signal to noise ration (SNR) : ≥ 80 dB (measurement bandwidth from 10 Hz to 2 kHz)
Common-mode voltage (CMV) range : ± 5 V
Common-mode rejection ratio (CMRR) :> 60 dB (at 50 / 60 Hz)
Crosstalk attenuation : Typically 60 dB
Auxiliary input channel – used as a tachometer input
Triggering method :Crossing of threshold on rising edge of signal
Triggering threshold (rising edge) : 2/3 of peak-peak value
Voltage range : ± 30 VRMS / ± 42.4 VAC ( PEAK ) or 60 VDC