560CVD03 Multimeter, 1A/5A, 3U3I
CT/VT Interface with 3 Voltage and 3 Current Inputs for Direct Monitoring of 3-Wire 85…. .400 VAC
1/5 A input for AC transformer
RTU500 serial interface (RS-485)
APPLICATIONS
The multimeter 560CVD03 is used to monitor input signals from three independently phased 3-wire or 4-wire connections.
Voltage, current and power can be measured directly for each phase and a number of other parameters can be derived via software. The measurement results are transmitted to the RTU560.
Leave a comment
Your email address will not be published. Required fields are marked *