Introduction
The GE Multilin 515 Blocking and Test Module has the following features:
• 14 Pole switchbank
• CT inputs short when current switches are opened
• Current injection for each phase
• Ground terminal
• Ability to visually isolate (open) trip relay output circuits
• Cover provided
• Suitable for utility and industrial use
• 515 test plugs available
Description
The 515 Blocking and Test Module provides an effective means of trip blocking,
relay isolation and testing of GE Multilin relays. By opening the switches and inserting test plugs,
phase and residual currents from the primary CTs can be monitored.
Currents can be injected into the relay from a secondary injection test set during commissioning.
Prior to testing, the trip and auxiliary circuits must first be opened to prevent nuisance tripping;
CTs can then be shorted. Conversely, when the test is complete and the relay put back into operation,
the CT switches should be closed first to ensure normal operation of the relay, prior to closing the trip and auxiliary circuits.