Locations for Field Control
The Profibus Bus Interface Unit and Field Control I/O modules can be located on
equipment, in junction boxes, inside panels, behind operator stations, and in other
locations where space is limited. The area should be clean, free of airborne contaminants,
and provide adequate cooling. Field Control modules can be installed in NEMA
enclosures. The enclosure can be as little as 4 inches (10.16 cm) deep. A 35mm x 7.5mm
DIN rail is required.
The Bus Interface Unit Terminal Block and up to four I/O Terminal Blocks are grouped
together using the connection cables provided. All of the I/O Terminal Blocks in a group
must be connected either before or after the Bus Interface Unit. A Bus Interface Unit
may not be connected between I/O Terminal Blocks.
Conformance to Standards (GFK-1179). This manual describes the installation
requirements for programmable control products used in industrial environments,
specifically, in situations where compliance to standards or directives from the
Federal Communications Commission, the Canadian Department of
Communications, or the European Union is necessary. The information in this
manual is applicable for GE Fanuc Series 90-70 and Series 90-30 programmable
controller products, Genius I/O products, and Field Control Distributed I/O and Control products.