DualControl (Power Bridge Warm Backup)

The EX2100e Regulator system is available in a warm backup (WBU) configuration,

which includes dual exciter control I/O and protection. The control includes M1 (Master

One) and M2 (Master Two), with two IGBT bridges that can accept separate or shared ac

input power. The control configuration can also share a common dc output circuit to the

exciter field through the transfer module. M1 and M2 are independent controls, each with

automatic and manual regulator functions. Either M1 or M2 can control bridge firing, as

determined by the operator. In the WBU configuration, M1 controls bridge #1. and M2

controls bridge #2.

To process application software, two independent Universal Controller Stand-alone Board

Version B (UCSB) controllers, with separate PCMs and an output selector module (SCM

or TCM), provide the dc output current for the exciter field (or SCTcontrol winding).