IEC 61850 (MMS)
The IEC 61850 MMS interface will allow data from Intelligent
Electronic Devices (IEDs) such as motor protection relays,
motor starters, motor control centers, switchgear, and similar
MMS-based devices to be integrated into DeltaV. The MMS
interface will be a client reading and writing data from/to the
Intelligent Electronic Device which acts as the server.
The EIOC only supports reading and writing of real time
signals using this protocol. Reading historical data or
Goose applications are not supported.
OPC UA Client
The OPC UA Client in the EIOC provides native client
implementation of a Data Access profile (real time data)
compliant with OPC UA version 1.03. The OPC UA client will
read and write up to 30,000 real time signals coming from
up to 64 OPC UA servers.
EtherNet/IP Control Tag Integration protocol
The EtherNet/IP Control Tag Integration protocol utilizes
EtherNet/IP Class 3 messaging to provide integration with
tag-based PLC data sources. Referencing data by tag name
eliminates the need for register mapping. Read or write up
to 10 signals per tag, and up to 2000 tags per EIOC for a total
of 20,000 signals. The EtherNet/IP Control Tag Integration
protocol supports reading string type signals and read/write
of arrays up to 64 elements each (max 100 arrays per EIOC).
The EtherNet/IP Control Tag Integration protocol supports
integration with ControlLogix and CompactLogix PLCs utilizing tags.