EIOC Configuration

The EIOC is configured in the I/O network level of DeltaV

Explorer and it does not count towards the controller node

count limit (limited to 60 EIOCs per system). The hierarchy

of the EIOC in DeltaV Explorer consist of:

„ EIOC

z Assigned Modules – Modules configured and running

inside the EIOC.

z Hardware Alarms – Hardware alarms associated with

the EIOC.

z PO1 – EIOC port, where the Ethernet Device Network

and protocol is setup.

z PDT – The Ethernet Devices are added and configured

under the EIOC port as Physical Devices (PDTs).

The amounts of PDTs that can be configured will vary

depending of the protocol selected in the port and

the amount of device licenses assigned. The PDTs can

be renamed.

z LDT – Logical Devices (LDTs) are added under the PDTs to

configure signals or control tags depending of the protocol

that has been selected at the port level. DST licenses are

applied at this level.