Accuracy:

Voltage mode: 0.125% of full scale from 0° to 60°C

Current mode: 0.225% of full scale from 0° to 60°C

Digital Filtering Time Constant: 0.3 Sec

DC Input Resistance:

Voltage mode: 780kW

Current mode: 250W

Repeatability: 0.003125%

Common Mode Rejection:

>120db @ 60Hz (digital filtering disabled)

Normal Mode Rejection:

>40db @ 500Hz (digital filtering enabled)

Isolation:

1500VDC channel-to-PLC

140Vrms channel-to-PLC

Output Specifications:

Output Channels: 4 analog output channels

Output Range:

Unipolar: 0 to 5VDC, 0 to 10VDC, 0 to 20mA

Bipolar: -5 to +5VDC, -10 to +10VDC, or -20 to +20mA

Resolution:

Unipolar 12 bits:

0 – 5VDC range = 1.25mV/step

0 – 10VDC range = 2.5mV/step

0 – 20mA range = 5µA/step

Bipolar 12 bits:

-5 to +5VDC range = 2.5mV/step

0- 10VDC range = 5.0mV/step

-20 to +20mA range = 10µA/step

Accuracy:

Voltage mode: 0.125% of full scale from 0° to 60°C over total load range

Current mode: 0.225% of full scale from 0° to 60°C over total load range

Capacitance Drive: 0.01 microfarad

Load Resistance:

Voltage mode: 1kΩ minimum, no maximum

Current mode: 0kΩ to 1kΩ max. @ 24VDC

or greater

User Supply: 20 to 30VDC @ 0.25 Amps

(maximum ripple of 0.4V)

UL Class 2 power supply

Isolation:

1500VDC channel-to-channel

1500VDC channel-to-PLC