Features

The 2500-ADP1 cable allows for the following conversions

field wiring:

– 500-5037A 8-channel analogue input connector to CTI 2558 8-channel analogue input 40F connector.

– 500-5047A 8-channel analogue output connector to CTI 2562 8-channel analogue output 40F connector.

Instructions

Method A – Installing a New Module into an Existing 500 Series I/O Adapter

Chassis

1. Disconnect power to the Series 500 chassis

2. Remove the 500-5037A/47A to be upgraded. 

3. Install the 2500-IADP into the slot where the 500 module was removed.

4. Configure the 2558/2562 to match the 500 module to be replaced .

5. Install the 2558/2562 into the 2500-IADP .

6. Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector.

(The screen label on the 2500-ADP1 indicates a 5037A / 5047A field wiring connector).

Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector.

(The screen label on the edge card connector shows pin 1 and pin A.)

7. Remove any 250 ohm resistors that may be installed in the 5037A / 5047A field wiring connector. 2558 / 2562 do not require these resistors.

8. Connect the 40F connector to the 2558/2562.

9. Restore power to the rack.

Method B – Installing a New Module into a New 2500 SeriesTM Base

1. Disconnect power to the 500 Series chassis. 

2. Remove the 500-5037A/47A to be upgraded.

3. Configure the 2558/2562 to match the 500 module to be replaced. 

4. Install the 2558/2562 into the 2500 SeriesTM base.

5. Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector (The screen label on the edge card connector shows pin 1 and pin A.)

6. remove any 250 ohm resistors that may be installed in the 5037A / 5047A field wiring connector. 2558 / 2562 do not require these resistors.

7. Connect the 40F connector to the 2558 / 2562. 

8. Restore power to the rack.