The Analog Input (AI), Analog Output (AO), and Analog
Input/Output (AI/O) modules provide the ControlWave®
Micro with the ability to monitor and control various analog
field signals. The following AI, AO, and AI/O modules are
available.
6 Analog Inputs and 2 Analog Outputs module
6 Analog Inputs module
8 Isolated Analog Inputs module
4 Isolated Analog Outputs module
All I/O modules have surge protection that meets C37.90
1978 and IEC 801-5 specifications.
6 Analog Inputs and 2 Analog
Outputs Module
The 6 Analog Inputs and 2 Analog Outputs module provides
six analog inputs and two analog outputs. Analog inputs are
externally sourced, single-ended, and individually jumper
configurable for either 4 to 20 mA or 1 to 5 Vdc operation.
Analog outputs are externally sourced (11 to 30 Vdc) and
individually jumper configurable for 4 to 20 mA or 1 to 5
Vdc. Surge suppression between each signal and ground is
achieved with 30 Vdc transorbs. The 6 Analog Inputs and 2
Analog Outputs module is available with local or remote
terminations.
Leave a comment