The Analog Input (AI), Analog Output (AO), and Analog

Input/Output (AI/O) modules provide the ControlWave®

Micro with the ability to monitor and control various analog

field signals. The following AI, AO, and AI/O modules are

available.

6 Analog Inputs and 2 Analog Outputs module

6 Analog Inputs module

8 Isolated Analog Inputs module

4 Isolated Analog Outputs module

All I/O modules have surge protection that meets C37.90

1978 and IEC 801-5 specifications.

6 Analog Inputs and 2 Analog

Outputs Module

The 6 Analog Inputs and 2 Analog Outputs module provides

six analog inputs and two analog outputs. Analog inputs are

externally sourced, single-ended, and individually jumper

configurable for either 4 to 20 mA or 1 to 5 Vdc operation.

Analog outputs are externally sourced (11 to 30 Vdc) and

individually jumper configurable for 4 to 20 mA or 1 to 5

Vdc. Surge suppression between each signal and ground is

achieved with 30 Vdc transorbs. The 6 Analog Inputs and 2

Analog Outputs module is available with local or remote

terminations.