Identify Module Features
Refer to the following figure to identify the hardware components of the 56AMXN/B module.
The module has:
• A label to indicate that it is a scanner for AutoMax
DCSNet and remote I/O
• A 4-character scrolling display (XXXX)
• 3 LEDs, labelled NET, CLX, and OK, to indicate the
status of the network, the connection to the ControlLogix processor, and its own internal state
• a 9-pin D-shell connector to connect to the DCS or remote I/O network
• switches at the top of the module to set the mode of operation and the drop number and drop depth
Set the Network Type and Node Address Switches
Before you install the module, you must set the network type, drop number and drop
depth using the switches at the top of the module.
The two switches at the left set the drop depth, the two at the right set the drop number.
The following table shows how to set the switches for each mode of operation.
For example, to configure the 56AMXN/B as a DCS slave with drop number 17,
drop depth 5, set the switches to 0, 5, 1, and 7 from left to right.
Any other settings are invalid and result in the module going into “Thumbwheel
test” mode. In thumbwheel test mode, the display shows the current switch settings.
It doesn’t go out of thumbwheel test mode until you cycle power.