Prosoft On Ethernet, the AN-X supports up to 16 Ethernet/IP connections

On remote I/O the AN-X module supports:

• Baud rates 57.6. 115.2. and 230.4 Kbaud

• Rack numbers 0 to 76 octal

• Block transfers at all allowable locations

On Ethernet, the AN-X supports up to 16 Ethernet/IP connections. Each Ethernet adapter

and the associated discrete I/O requires one connection. Each analog module requires one

connection. In some cases, a discrete module will require a separate connection, for

example, if desired functionality is available only if the module has its own connection.

The AN-X2-ABRIO-EIPSCN module has a web interface for configuring the module, for

monitoring logs and for performing administrative functions. You can communicate with

the module using any standard web browser such as Internet Explorer.

The module firmware can be selected and updated using the web interface. 

Refer to page 41 for details.

A watchdog timer is implemented in the module’s hardware. If the firmware does not

kick the watchdog within the timeout period the watchdog times out and places the

module into a safe fatal failure state.

A jabber inhibit timer is implemented in the module’s hardware. If the network

transmitter is on longer than 150% of the longest network frame time, the transmitter is

forced off and the module is placed into a safe fatal failure state.

Prosoft The AN-X emulates a ControlLogix scanning I/O over Ethernet

The AN-X emulates a ControlLogix scanning I/O over Ethernet.

All configuration data comes from the AN-X, not from remote I/O. Configuration

options correspond to what’s available in a ControlLogix, not to what is available in

remote I/O. No configuration data gets passed from remote I/O to Ethernet. If your

program dynamically changes configuration data, or if it contains logic to configure a

module, the program will have to be modified to remove or disable that logic.

You may need to make some changes to the control application related to addresses, logic

and timing.

Some behaviour that is set by switches on the remote I/O adapter is set in parameters for

Ethernet modules. For example, hold last state is set on a module-by-module basis when

you scan over Ethernet.

In addition, you may need to make changes because Ethernet does not support

complementary I/O, or standard 32 or complementary 32 addressing.

For example, 32 bit discrete Flex I/O modules require a separate Ethernet connection.

You must communicate with them from remote I/O using block transfers, not as discrete data.

Prosoft AN-X2-ABRIO-EIPSCN Module Overview

AN-X2-ABRIO-EIPSCN Module Overview

The AN-X2-ABRIO-EIPSCN communications module connects a scanner such as a

PLC-5 on an Allen-Bradley remote I/O network to I/O modules on Ethernet/IP.

As parts become obsolete and remote I/O adapters become unavailable, the

AN-X2-ABRIO-EIPSCN is a solution that lets you retain the original controller, I/O

modules and field wiring and replace remote I/O adapters with Ethernet adapters. The

existing remote I/O scanner talks to the AN-X, which maps discrete and analog I/O on

remote I/O to Ethernet data.

Some behaviour that is set by switches on the remote I/O adapter is set in parameters for

Ethernet modules. For example, hold last state is set on a module-by-module basis when

you scan over Ethernet.

In addition, you may need to make changes because Ethernet does not support

complementary I/O, or standard 32 or complementary 32 addressing.

For example, 32 bit discrete Flex I/O modules require a separate Ethernet connection.

You must communicate with them from remote I/O using block transfers, not as discrete data.

Prosoft EtherNet/IP™ to Remote I/O Hardware Specifications

Hardware Specifications

Ports

1 RJ45 10/100 Mbps Ethernet port

1 Phoenix 3-pin power connector

1 Phoenix 3-pin connector network connector

Typical Power Consumption

200 mA @ 12 VDC or 100 mA @ 24 VDC

Maximum Power Dissipation

2.4 W

Operating Temp

32°F to 122°F (0 ºC  to 50 ºC)

Storage Temperature -40°F to 185°F (-40 ºC  to 85 ºC)

Dimensions

107 x 126 x 34 mm

(4.18 x 4.97 x 1.33 in)

Not including connectors

Humidity

5% to 95% RH, with no condensation

Prosoft EtherNet/IP™ to Remote I/O or DH+ Gateway AN-X2-AB-DHRIO DH+

Remote I/O Scanner

This mode allows users to replace their existing Remote I/O PLC with a ControlLogix or CompactLogix PAC without having to

replace existing racks of I/O.

 Build new controller program without interrupting existing controls, minimizing downtime

 Supports up to 32 racks of Remote I/O

 Supports all Remote I/O baud rates (57.6. 115.2. and 230.4 K baud), and Remote I/O addressing 0 to 76 octal

 Works with both ControlLogix or CompactLogix

 Auto-Configuration utility discovers baud rate and maps discrete I/O reducing configuration errors

DH+

This mode acts as a bridge between an EtherNet/IP and a Data Highway Plus network.

 Programming terminals, and/or processors on an EtherNet/IP network can access legacy processors on a DH+ network

 Download to a PLC5 or SLC through RSLinx

 Configures through web browser

 Supports all DH+ baud rates (57.6. 115.2. and 230.4 K baud)

 Support for DH+ to EtherNet/IP PanelViews upgrades on PLC5 or SLC networks

Flex I/O Scanner

This mode allows PLC’s on Remote I/O to connect to and control 1794-AENT EtherNet/IP Flex adapters.

 Designed to replace obsolete 1794-ASB adapters

 Supports up to 16 EtherNet/IP connections

 Each adapter and rack of discrete count as a single connection. Each analog module counts as a single connection

Prosoft EtherNet/IP™ to Remote I/O or DH+ Gateway AN-X2-AB-DHRIO

The AN-X2-AB-DHRIO Gateway is designed to help customers initiate

a phased migration approach to replacing or upgrading legacy Remote

I/O PLCs, HMI’s, Drives or Flex I/O Adapters. These solutions can be

achieved by selecting the corresponding operation mode during initial

configuration. The AN-X2-AB-DHRIO has a built-in web server that can

display diagnostics data, configuration, upload configuration files, and

set the operation mode.

Note: Now supports DH+ migrations on SLC networks. Some PLC

code change may be required see TN143269-001 DH+ to EIP PV

Migration for SLC networks.pdf for more information.

DRIVE

This mode supports upgrading legacy Allen Bradley drives on Remote I/O to new EtherNet/IP enabled

drives.

 No changes to PLC code required

 Supports up to 4 EtherNet/IP drives

 Configurable with 1/4. 1/2 and full rack addressing

 Supports all PowerFlex drives on EtherNet/IP

HMI

This mode allows legacy PanelViews on Remote I/O or DH+ to be upgraded to a PanelView Plus, PanelView Plus 6 or PanelView

Plus 7 on EtherNet/IP.

 No changes to PLC code required

 Supports up to 8 PanelViews on the same network

 Support for DH+ to EtherNet/IP PanelViews upgrades on PLC5 or SLC networks

Prosoft MVI69-PDPS PROFIBUS DP Slave Communication Module

General Specifications

– Single slot – 1769 backplane compatible

– Module is treated as an input/output module with access to processor memory for data transfer

between the processor and the module

– Ladder logic is used to transfer data between the module and the processor. A ladder example file is

included.

– Obtains configuration data from a configuration text file downloaded to the module. Sample

configuration file included.

– Supports CompactLogix and MicroLogix 1500 LRP controllers except 1769-L23E-QBFC1B, 1769-L16x,

and 1769-L18x.

Functional Specifications

PROFIBUS slaves have access to the input and output images of the device with up to 122 words of input

and output data and up to 200 words in total.

– All standard baud rates up to 12 Mbps are supported.

– Configuration data is stored in the non-volatile memory of the MVI69 module

– Supports extended diagnostic data (DPV0)

– Automatic baud rate detection at all valid PROFIBUS V0 baud rates

– Multiple modules in one rack

Other Products

ProSoft Technology offers a full range of hardware and software solutions for a variety of industrial

communication platforms.

Prosoft PLX31-MBTCP-SIE Industrial Ethernet Communication Gateway

ProSoft Technology’s Modbus® TCP/IP to Siemens Industrial Ethernet Gateway allows for

high-speed bi-directional data transfer between Modbus® TCP/IP controllers and Siemens® S7-400. S7-300. S7-200. S7-1200 and S7-1500 PACs.

In addition, the gateway has a number of features, including data prioritisation, that simplify integration, reduce commissioning time and optimise performance.

Functions

 The ProSoft Discovery Service utility allows your PC to view the gateway and edit its default IP address without being on the same subnet.

 Supports up to 20 simultaneous client and server connections to speed communications between devices such as HMIs, SCADA systems, power monitors, and traffic computers.

 In addition to S7 controllers, the Gateway can also be used with Siemens® S5 controllers with corresponding interfaces.

 The Gateway includes an SD card slot (SD card optional) for storing dcs-sis.com configuration files. It can be used for disaster recovery.

 Safe module configuration via Module Switch (v1.04 and higher).

 can exchange large amounts of data using up to 10.000 16-bit registers.

Specification Description

Power Supply 24 VDC nominal

10 to 36 VDC allowed

Positive, negative, ground terminals

Current Load 24 VDC nominal @ 300 mA

10 to 36 VDC maximum @ 610 mA

Operating Temperature -25°C to 70°C (-13°F to 158°F)

Storage Temperature -40°C to 80°C (-40°F to 176°F)

Shock IEC 60068-2-27; 15G @ 11ms, 3 axes (in operation)

IEC 60068-2-27; 30G @ 18ms, 3 axes (non-operating)

Vibration IEC 60068-2-6; 5G @ 10 to 150 Hz

Relative humidity 5% to 95% RH, non-condensing

Dimensions (H x W x D) 5.38 x 1.99 x 4.38 in.

13.67 x 5.05 x 11.13 cm

LEDs Configuration (CFG), Error (ERR), Power (PWR), Hardware Failure (FLT), Network Connection (FLT).

Error (ERR), Power (PWR), Hardware Failure (FLT), Network Status (NS), EtherNet/IP™ Class I or Class

Module Status (MS),

Module Configuration Status (EtherNet/IP only) Ethernet

Communication Port Link/Active and 100 mbit

Ethernet ports 10/100 Mbit full-duplex and half-duplex RJ45 connector Galvanic isolation

Isolation 1500 Vrms, 50 to 60 Hz for 60 seconds, applied according to section 5.3.2.

Applied in accordance with IEC 60950 Section 5.3.2: 1991 Ethernet Broadcasts

Storm recovery capability of less than or equal to 5000 [ARP] frames per second for less than or equal to 5 minutes.

2.5 mm screwdriver J180 power connector included with each unit

Prosoft PTQ-PDPMV1 PROFIBUS DP Master Network Interface Module

Configuration

ProSoft Configuration Builder (PCB) provides a PC-based software configuration solution for managing module configuration files and viewing communications and network diagnostics.

The PCB is a powerful solution not only for new configuration dcs-sis.com files, but also for importing configuration information from previous installations (known jobs) into new projects.

General Specifications

– Single slot – Quantum backplane compatible

– Module is recognised as an option module with access to PLC memory

for data transfer

– Configuration data is stored in the ProTalk® module’s non-volatile memory

– Microsoft Windows XP, 2000 and NT configuration software included with module

– Up to six modules can be placed in a rack

– Local rack – modules must be placed in the same rack as the processor

– Compatible with all common quantum programming software packages, including Concept

(version 2.6 or later), Unity Pro (version 2.2 or later), ProWORX (version 2.20 or later) (HSHS)

or higher) (HSBY for Unity Pro environments only)

– Quantum data types supported: 3x, 4x

– High-speed data transfer on the backplane provides fast data update times

– Sample ladder files available

Functional Specifications

– Easy-to-use bus view drag-and-drop configuration interface via ProSoft

Configuration Builder software (see PSW-PCB datasheet)

– Monitors and modifies process data and DPV1 acyclic data, and provides online slave diagnostics

– Supports PROFIBUS PA slaves on the network via DP/PA coupler or link

– Supports up to 125 slave devices via repeaters

– Supports extended diagnostic data (DPV1)

– Supports all standard baud rates up to 12 Mbits/s

– Automatic baud rate detection at all valid PROFIBUS DPV1 rates

– Supports parameter read/write operations according to PROFIdrive 3.1 standard

– Supports synchronisation and freeze commands

– Alarm indication and acknowledgement processing (DPV1)

– Support for multicast and broadcast messages (DPV1)

– Conformity of the slave configuration to the processor determined by CRC checksums

– Includes FDT/DTM PROFIBUS master transport communication DTM software (part number PSW-CDTM-PDPM)

Prosoft RLX2-IHNF 802.11abgn Fast Industrial HotSpot™

The ProSoft Technology Rapid Industrial Hotspot (RLX2-IHNF) provides secure wireless solutions for factory floor, SCADA automation,

SCADA automation, process control systems and mobile worker Wi-Fi infrastructure.

It operates in 2.4 or 5 GHz bands, including DFS channels, for indoor or outdoor applications.

The hotspot supports access point, repeater and client modes. 802.11n technology provides fast data rates of up to 300 Mbps.

This provides excellent packet-per-second performance and robust communications in harsh industrial environments.

802.11n MIMO and channel bonding support demanding wireless applications such as Ethernet I/O and high-resolution video.

The included IH Browser configuration and monitoring dcs-sis.com software allows users to view network topology, assign IP addresses, monitor network diagnostics and update radio firmware.

The optional OPC Diagnostic Server is ideal for managing wireless SCADA networks over long distances.

Features and Benefits

EtherNet/IP™ or Modbus® based PLC/PACs can use message commands to read diagnostic information from the radio, helping to reduce downtime when troubleshooting wireless networks.

802.11i, WPA-2 Personal/Enterprise with 128-bit AES encryption secures the network RADIUS security secures the network with advanced authentication and encryption Virtual Local Area Networks (VLANs) enable secure network segmentation

Network Address Translation (NAT) eliminates the need for machine builders to change IP addresses every time a machine is deployed

Quality of Service (QoS) provides data prioritisation for I/O control devices, video data, etc.

Ultra-fast roaming (less than 10 milliseconds) maintains seamless, high-speed connectivity with one or more devices on mobile equipment and machines such as cranes, AGVs, and transporters as they move between access points

IGMP snooping and packet filtering optimise UDP multicast traffic for superior EtherNet/IP I/O communications

Supports communication with multiple Ethernet devices when used with existing third-party wireless infrastructure

Supports AeroScout RTLS (Real-Time Location Service) tags by passing signals from the tag to the network

Supports Power over Ethernet (PoE) to reduce cabling costs

Disaster recovery feature allows radio configurations to be stored on a microSD card for quick replacement in the field

Serial network connectivity (Modbus, DNP 3. etc.) via 802.11 wireless network

Simple local and remote configuration, monitoring and wireless network diagnostics via IH browser utility or SNMP