Honeywell FS24X Detector True triple IR wide band sensing and sophisticated detection algorithms

FS24X Detector

True triple IR wide band sensing and sophisticated detection algorithms.

FS24X provides wideband Multi-Spectrum Triple IR (IR/IR/IR/Visible) flame detection.

It is part of our FSX family of advanced technology Electro-Optical fire detectors.

Using our patented* WideBand IR™, WideBand 4.3 micron IR™, and Visible detection technology,

the FS24X sets the standard for flame detection.

Sophisticated software algorithms and dual microprocessors ensure that the FS24X

has the highest fire detection performance combined with optimal false alarm rejection.

The WideBand IR™ Infrared technology using high-speed solid-state

Quantum sensors allows detection of all types of fires,

hydrocarbon and non-hydrocarbon, in all weather conditions.

Dual microprocessors provide a high level of fail-safe operation combined

with fast and reliable performance. The master microprocessor performs

high-speed digital sampling and signal-processing calculations, while

the slave microprocessor handles  various sensor data, performs

communications, self-diagnostics and provides interface versatility and

additional memory for storing Event Log and FirePic™ data.

Honeywell FS20X BENEFITS

BENEFITS

• Detects hydrocarbon and non-hydrocarbon fuel fires in all environmental conditions

• Wide operating temperature range

• Arc welding immunity

• False alarm rejection

• Minimal maintenance for trouble-free operation

• PC software and interface module (FSIM) for fault diagnostics real-time graphs (RTGs),

and downloading of FirePics™ and event log

• Suitable for a wide variety of applications

Honeywell FS20X Flame Detector FEATURES

General Specification

• High RFI and EMI immunity

FEATURES

•  Patented WideBand IR™ Infrared combined with Ultraviolet

• Detection range greater than 60 m (200 feet)  to 0.1 m2 (1sq. ft.) heptane fire

• Patented Electronic Frequency Analysis

• Visible sensor for optimum false alarm rejection

• Selectable detection sensitivities

• Solar blind 90° field of view

• Dual microprocessors for reliable performance

• Real-time clock for accurate time dating of events

• FirePic™ — Up to 6 pre-fire event data storage

• Event log — Up to 200 events with date and time stamp

• Built-in RS-485 ModBus communication

• Built-in non-isolated 4-20 mA analog output (sink or source)

• Alarm, Fault and Fire Verification relays

• Automatic Optical Path and Electronic self-test

• Patented Electronics Module for component protection with plug-in terminations for easy  field

installation

• Two M25 conduit entries

• Low power consumption

• FM hazardous area approved

• Ex d ATEX /IECEx approved

• CU-TR approved

• INMETRO approved

• Meets SIL 2 requirements

• Certified to EN54-10:2002

• FM 3260 performance

Honeywell The FS20X detector is a Multi-Spectrum

The FS20X detector is a Multi-Spectrum and UV/Dual IR/VIS and flame detector

with a proven UV solar-blind sensor. FS20X delivers a faster response and

fewer false alarms, performs in a wider ambient temperature range,

with a much longer detection range compared to conventional UV/IR detectors.

Conventional and older technology UV/IR detectors, using narrow band

4.3 micron IR sensors, will not always respond to smoky fires or if the

detector lens is contaminated with oil and other substances since both

UV and 4.3 micron signals are attenuated, obscured or absorbed by thick

smoke or detector lens contaminations. All UV sensors will be attenuated to some degree.

Superior Technology Dual microprocessors enable fast and reliable performance.

The master microprocessor performs high-speed digital sampling

and signal processing calculations while the slave microprocessor handles sensor data,

performs communications, self-diagnostics and manages interfaces and memory

for storing event log and FirePic™ data. The FS20X detector has a detection range

in excess of 60 m (200 feet) (very high sensitivity setting) for the detection of a

0.1m2 (one square-foot) Heptane reference fire and has a field of view with a greater volumetric

coverage than most UV/IR detectors.

This means fewer detectors can be used to cover an area as compared to other manufacturers’ detectors.

The FS20X detector using advanced algorithms for signal processing and fire and flame analysis to

alarm to most  fires in all industrial environmental conditions. If the detector’s UV signal is degraded

due to heavy smoke or a contaminated lens, FS20X’s patented WideBand IR™, Near Band IR and

Visible sensors will still alarm to fire, albeit at a reduced sensitivity and slower response time.

Honeywell FS20X Detector Advanced Multi Spectrum (UV/Dual IR/VIS) Flame Detector

FS20X Detector

Advanced Multi Spectrum (UV/Dual IR/VIS) Flame Detector.

Based on the foundation of the highly successful and reliable SS4 detector,

the FS20X detector represents a quantum leap in integrating Infrared

and Ultraviolet sensing technologies.

The FS20X detector is a Multi-Spectrum and UV/Dual IR/VIS and flame detector

with a proven UV solar-blind sensor. FS20X delivers a faster response and

fewer false alarms, performs in a wider ambient temperature range,

with a much longer detection range compared to conventional UV/IR detectors.

Conventional and older technology UV/IR detectors, using narrow band

4.3 micron IR sensors, will not always respond to smoky fires or if the

detector lens is contaminated with oil and other substances since both

UV and 4.3 micron signals are attenuated, obscured or absorbed by thick

smoke or detector lens contaminations. All UV sensors will be attenuated to some degree.

Superior Technology Dual microprocessors enable fast and reliable performance.

Woodward EGCP-3 HARDWARE SPECIFICATIONS

HARDWARE SPECIFICATIONS

Size:

Operator Interface Panel:

Power Supply Voltage:

Control Part Numbers:

Connectors:

Voltage Measuring Input Range:

Current Measuring Inputs:

Temperature Range:

Humidity:

Enclosure Rating:

Vibration:

Mechanical Shock:

Regulatory Compliance (pending):

281.8mm (11.1”) High x 358.1mm (14.1”) Wide x 134.0mm (5.275”) Deep

8 (20 Character) lines plus membrane keypad

24 Vdc system (18–32 Vdc nominal; 9–40 Vdc maximum)

DR: 8406-103

LS: 8406-113

MC: 8406-114

Terminal blocks are screwless CageClamp style blocks. PT and CT inputs

are fixed screw terminals.

70–300 Vac

5 Aac RMS nominal, 7 Aac RMS maximum –20 to +70 °C operating; –30 to +80 °C storage

95% at +60 °C non-condensing

Meets IP56 (IEC) and Type 4 (NEMA) requirements from the front panel and

properly installed in an equivalent enclosure

Suitable for engine skid or control cabinet

Random Test: 10–2000 Hz at 0.04 G²/Hz and 8.2 Grms PSD

30 g peak, 11 ms duration, non-operating

UL508; CSA Hazardous Locations Class I, Division 2. Groups A–D

IEC Zone 2 European Group IIC

EEC EMC Directive; EEC Low-Voltage Directive

Marine LR

RINA, ABS, and GL classifications

EGCP-3 Applications

• Single Unit—No Utility Parallel

• Single Unit—Utility Parallel

• Multiple Unit—No Utility Parallel

• Multiple Unit—Utility Parallel

• Multiple Unit—Multiple Utility Feeds Parallel

Woodward EGCP-3 Generator Protective Features

Generator Protective Features

• Over/Under Voltage (27.59)

• Over/Under Frequency (81O,81U)

• Directional (Forward/Reverse) Power (32)*

• Negative Phase Sequence Overcurrent (46)

• Negative Phase Sequence Overvoltage (47)

• Phase Overcurrent (51)*

• Directional VAR

• Phase Current Differential Imbalance (87)*

• Speed/Frequency Mismatch

• Load Surge

Utility Protective Features

• Over/Under Voltage (27.59)

• Over/Under Frequency (81O,81U)

• Directional (Forward/Reverse) Power (32)*

• Negative Phase Sequence Overcurrent (46)

• Negative Phase Sequence Overvoltage (47)

• Phase Overcurrent (51)*

• Voltage Restrained Phase Overcurrent (51V)*

• Directional VAR

• Phase Current Differential Imbalance (87)*

• Loss of Mains/Loss of Mains with Alarm

*—Inverse Time Protections implemented are according to IEEE C37.112 “Very Inverse” curves

Woodward EGCP-3 Generator System Control Package Functions

Reactive kVAR Control

• VAR (PF) sharing on isolated busses using percentage based reactive load sharing

• Voltage bias signal to AVR configurable for discrete raise/lower,4–20 mA, ±1. ±3. or ±9 Vdc

• Power factor or VAR control when base loaded

• Externally adjustable VAR or PF setpoint levels

• Manual voltage control capability

• Configurable load/unload ramp rates

Synchronizing

• Phase match or slip frequency synchronization with voltage matching

• Full three-phase sensing on both busses

• Manual synchronization capability

• Adjustable phase window, voltage window, reclose attempts, reclose timing

• Safe dead bus closing logic internal to the control

• Synch check (25)

• Breakers or contactors

Automatic Unit Sequencing

• Automatically starts and stops gen-sets based on plant bus demand

• Automatic generator set loading and unloading for bumpless transfer

• Configurable plant bus demand startstop levels and timers

• Configurable generator priority sequencing

Communications

• Modbus® RTU or DDE communications via RS232 (1 each) and RS-232/422/485 (2 each) serial ports

• Echelon® TP/XF-1250 network

• CAN 2.0b Network (OEM option only)

Woodward Custom OEM Configurations

Custom OEM Configurations

Among the many EGCP-3 control functions are:

Engine Control/Protection

• Configurable start sequencing

• kVA-controlled cool-down timer

• Oil pressure monitoring (idle/rated)

• Coolant temperature monitoring

• Battery voltage monitoring

• Speed monitoring with overspeed protection

Real kW Load Control

• True RMS power calculations

• Load bias signal to engine speed control, configurable for ±3 Vdc, 0–5

Vdc, 500 Hz PWM, 4–20 mA, discrete raise/lower

• Configurable loadunload ramp rates

• Isochronous load-sharing of up to 16 EGCP-3 units using percentage based load sharing

• Built-in import/export control

• Soft utility transfer function

• Externally adjustable load or process references

Woodward EGCP-3 is available in standard configurations

DESCRIPTION

EGCP-3 is available in standard configurations including:

DR—Distributed Resource:

• Single unit isolated

• Single unit parallel to mains

• Single unit ATS

LS—Load Share:

• Multiple unit isolated

• Multiple unit parallel to mains

MC—Master Controller:

• Mains tie breaker control

• Inter-bus tie breaker control

Features

• Complete generator system control package

• Automatic load demand sequencing of multiple units

• Three-phase synchronization

• Comprehensive system protection –engine, utility, and generator

• Revenue-grade power and energy metering

• Digital display of engine, generator, and system data

• Real kW and reactive kVAR load sharing and control

• Additional on board and distributed I/O available

• Easily adapts to exact application needs with GAP™ programming tools

• Advanced network communications

• DSLC™ compatible

• Built-in diagnostics