Hitachi Energy 560CVD11 Multimeter

Detection

Directional overcurrent detection is used to protect multi-source feeders to distinguish between

Directional overcurrent detection is used to protect multi-source feeders to distinguish between faults in different directions. The device has three-phase and neutral overcurrent detection.

It ensures 90° quadrant coordination during phase directional polarization. Therefore, regardless of whether the system is in fault-free or faulted operation.

The selected polarization voltage should be reasonably constant regardless of whether the system is operating without or with faults.

Phase-directed overcurrent

Phase-directed detection requires the determination of whether the current flow in each phase is forward or reverse, depending on the connection of the phase sources, the selected MTA angle, and the voltage and current phases.

Features

The multimeter is a microprocessor-based intelligent electronic device (IED) for measuring current, voltage, power and energy.

Fault current detection and overcurrent indication are also provided.

The current and voltage inputs are connected via transformers only (see Wiring). The modules support configurations with 3 or 4 voltage transformers and 3 or 4 current transformers.

The calculated values are scaled according to the constants programmed by the user for the current and voltage transformers. All values are updated after 200 ms.

Fault current can be measured up to 20 times the rated current.

The current input can withstand 50 times the rated current for 1 second.

The multimeter is equipped with two binary outputs, which are not supported in the RTU500 series configuration.

Hitachi Energy Analogue Output Module 520AOD01

Applications

Analogue control outputs for sequential or closed-loop control, display instruments, measurement recorders, etc,

The analogue output board 520AOD01 can be connected to measuring and recording instruments, etc.

The board 520AOD01 has 2 output channels which can be configured for different voltage or current output ranges.

The module 520AOD01 can process the following types of signals:

– Analogue setpoint commands

– Floating-point setpoint commands

The following output ranges can be configured independently for each channel via on-board switches:

– ± 2.5 mA

– ± 2.5 mA ± 5 mA

– ± 10 mA

– ± 20 mA (4…20 mA) .20 mA)

– ± 1.25 VDC

– ± 2.5 VDC

– ± 5 V DC

– ± 10 V DC

Output formats unipolar, bipolar or real-time zero (4 … 20 mA) are configurable via software parameters. 20 mA) can be configured via software parameters.

Hitachi Energy 520PTD01 Temperature Measurement Module (PT100)

Applications

The 520PTD01 circuit board is used for direct connection of PT100 temperature transmitters.

Up to six transmitters can be connected to the board. The measuring range is ± 200 °C.

Special features

Basic checks and calculation-intensive cyclic processing functions are already performed on the module, thus reducing the burden on the communication unit.

Relevant changes are transmitted as events via the WRB I/O bus.

The 6 differential inputs are not isolated from the RTU500 series power supply.

The 520PTD01 converts the analogue signal to 4096 steps (12 bits) and measures 100%.

The differential inputs are protected against static and dynamic overvoltage by protection circuitry. A low-pass filter suppresses non-line frequency AC interference.

Two additional channels are used for automatic zero calibration.

The line frequency is configurable in the configuration tool.

The microcontroller uses these configuration parameters to set up the A/D converter.

The microcontroller controls the A/D converter and performs all processing functions on the configured measurements within a conversion time of 80 ms (50 Hz).

In addition, the microcontroller communicates with the RTU system bus. All configuration features and processing parameters are downloaded from the CMU via the RTU system bus.

The module is connected to the RTU WRB I/O bus (wired OR bus) via adapter 520ADD01.

During initialisation and operation, the module performs a series of tests. If a fault occurs, it will be reported to the CMU.

All fault conditions affecting the functionality of the module are displayed as general fault signals with the red LED “ERR”.

Module faults are detected by the communication unit.

Hitachi Energy 520ADD01 Input/Output Adapter

520ADD01 Input/Output Adapter

DIN rail mounting base module RTU540

Expansion of wired or bus (WRB) with additional RTU520 I/O modules

Number of modules selectable via front jumper (4 or 8)

Inputs: WRB, ribbon cable

Outputs: WRB, ribbon cable

Applications

I/O adapter 520ADD01 for connecting RTU520 I/O modules to RTU520 or RTU540 communication modules

Features

The I/O adapter connects to the WRB I/O bus (wired OR bus) and automatically generates the address of the connected I/O module within the I/O assembly.

Two green LEDs on the module indicate activity on the I/O bus.

Hitachi Energy 520ADD02 Input/Output Adapter

520ADD02 Input/Output Adapter

Extends WRB to decentralised locations

Number of modules selectable via front jumper (4 or 8)

Input: WRB

Output 1: Fibre optic interface (multimode)

Output 2: RS485

Applications

I/O adapter 520ADD02 for connecting more than 16 RTU520 I/O modules to the

RTU520 or RTU540 to an I/O bus with RS485 or fibre optic connection.

The adapter can also be used to extend the WRB I/O bus in decentralised I/O applications.

The maximum distance is up to 2 kilometres and the distance between the I/O adapters needs to be more than 30 cm.

In addition, I/O adapter 520ADD02 can be used as a stand-alone module to extend the RTU560 I/O modules (e.g. 23BE40. 23BE40. 23BE40. 23BE40. 23BE40. 23BE40. 23BE40. 23BE40. 23BE40. 23BE40).

(e.g. 23BE40. 23BE50. 23BA40) to the RTU540.

The module is available in two versions (standard)

– R0001: RS485

– R0002: RS485 and glass fibre optics, 840 nm

Hitachi Energy Input/Output Adapter 520ADD03

520ADD03 Input/Output Adapter

Converts RS485 or fiber optic connections to WRB in decentralized locations

Requires 520PSD01

Supports up to 16 I/O modules

Applications

I/O adapter 520ADD03 for connecting more than 16 RTU520 I/O modules to RTU520 or RTU540 with RS485 or fiber optic connection

or RTU540 with RS485 or fiber optic connections.

The adapter can also be used to extend the WRB I/O bus in decentralized I/O applications over distances of up to 2 km.

The distance between the I/O adapters needs to be more than 30 centimeters.

In addition, I/O adapter 520ADD03 is used to connect the RTU520 I/O module to the RTU560.

The I/O adapter is always used with the power supply unit 520PSD01.

The module is available in two versions (standard)

– R0001: RS485

– R0002: Glass fiber, 840 nm

Features

The I/O adapter is the first adapter in the DIN rail mounted I/O assembly and it starts with a new virtual rack number.

The adapter converts the SPB I/O bus (Serial Peripheral Bus) with RS485 or fiber optic connection to a WRB I/O bus.

The glass fiber optic module is compatible with the 23OK24 and 560FOC40 modules.

There are two green LEDs on the module to indicate activity on the I/O bus.

The virtual rack address is selectable via DIP switches. In addition, the adapter automatically generates I/O module addresses within the I/O assembly.

Hitachi Energy 540CID01 DIN Rail Mount Base Module

Applications

The 540CID01 is a module in the RTU540 product family consisting of a communication unit (CMU), a multiple input/output module (IOM) and a galvanically isolated wide-range power supply (IOM).

The 540CID01 is a module in the RTU540 product family consisting of a communication unit (CMU), a multi-input/output module (IOM), and a galvanically isolated wide-range power supply (PSM) in a DIN rail metal housing.

Key tasks include

– Managing and controlling the RTU520 I/O module via the serial I/O bus

– Reading process events from the input modules

– Sending commands to the output modules.

– Communication with the control system and the local HMI system via serial and Ethernet interfaces.

– Communicates with sub-RTUs, IEDs, or multimeter devices via serial and Ethernet interfaces.

– Manages the time base of the RTU540 product line station and synchronizes the I/O modules.

– Handles the dialog between the RTU540 product line and a web browser via LAN and USB interfaces.

– Acquisition of 8 analog input signals (mA or V signals) with a fast scan cycle of 100 ms for 2 inputs – Acquisition of 16 digital input signals with a fast scan cycle of 100 ms for 2 inputs

Acquisition of 16 digital input signals, 1 high-speed counter input (max. 16 kHz)

– 8 output contacts (normally open), 1-pole or 2-pole outputs

The device is equipped with a battery-buffered real-time clock (RTC).

The device is available in two versions:

– R0001: Process voltage 24 … 60 V DC

– R0002: Process voltage 110 … 125 V DC 125 V DC

Hitachi Energy 540CMD01 Base Module

540CMD01: Base Module

DIN rail mounting base module RTU540:

Metal housing

4x Serial Ports (RS-232. RS-485)

2x Ethernet ports (10/100BaseT)

2x USB ports

Power supply 24…. .125 V DC

Connection interface with RTU500 I/O expansion module

Applications

The 540CMD01 is a module of the RTU540 product family consisting of a communication unit (CMU) and a galvanically isolated wide-range power supply (PSM).

The 540CMD01 is a module in the RTU540 product family consisting of a communication unit (CMU) and a galvanically isolated wide-range power supply (PSM) mounted in a DIN rail metal housing.

The main tasks are as follows

– Managing and controlling the RTU520 I/O module via the serial I/O bus

– Reading process events from the input modules

– Send commands to the output modules.

– Communication with the control system and the local HMI system via serial interface (RS232) and Ethernet 10/100BaseT interface.

– Communicates with sub-RTUs, IEDs, or multimeter devices via interface (RS485) and Ethernet interfaces.

– Manages the time base of RTU540 product line stations and synchronises I/O modules.

– Handles the dialogue between the RTU540 product line and a web browser via the LAN interface.

Hitachi Energy 560PSU40 Current Isolated DIN Rail Power Supply

DIN rail mounted power supply module

– Input voltage: 85…. .264 V AC or 85… .375 V DC

– Output voltage: 24 V DC, max. 2.5 A, 60 W 2.5 A, 60 W

– Power supply for up to 8 interconnected modules

Modules 23BEx0 / 23BA40 / 560FSMxx / 560MPR01 / 560CVDxx / RTU540 / RTU520

Applications

The power supply unit 560PSU40 is a galvanically isolated DIN rail power supply.

It is designed to power DIN rail I/O modules, mounting boards and communication modules.

The 560PSU40 is designed to power DIN rail I/O modules, mounting boards and communication modules of the RTU500 series.

For increased availability, two power supplies can be run in parallel. No external diodes are required.

Features

– Ultra-compact plastic housing

– Reliable DIN rail snap-in mounting

– Universal input: 85 – 264 V AC, 50/60 Hz, or 85 – 375 V DC

– Adjustable output voltage

– Good power supply signal

– Low ripple and low noise

– Overload and short-circuit protection

– Worldwide safety approvals

– Parallel operation possible

Hitachi Energy 560PSU41 Power Module RTU500 Series

560PSU41 DIN rail power supply for 24…. .60 V DC

Power supply module for DIN rail mounting

Output voltage: 24 V DC, max. 2.5 A, 60 W

Suitable for up to 8 plug-in modules 23BEx0/23BA40/560FSMxx/560MPR01

Power supply module for DIN rail mounting

– Input voltage: 24…. .60 V DC

– Output voltage: 24 V DC, max. 2.5 A, 60 W 2.5 A, 60 W

– 24 V DC power supply for DIN rail mounting

APPLICATIONS

The power supply unit 560PSU41 is a galvanically isolated DIN rail power supply.

It is designed to power DIN rail I/O modules and communication modules of the RTU500 series.

Features

– Ultra-compact plastic housing

– Reliable DIN rail snap-in mounting

– Universal input 24 – 60 V DC

– Adjustable output voltage