TRIP MULTIPLY
The most common use of this function is to prevent unwanted monitor alarms during certain
conditions of machine operation. In the operation of some machinery, it is impossible to avoid
some periods of “higher than normal” vibration. Examples include startup and coastdown,
especially if the operating speed is above rotor system balance resonances (“critical speeds”),
structural and other resonances, and changes in machine load or other operating conditions.
The Trip Multiply function causes the monitor alarm setpoints (both Alert and Danger) to increase
by a fixed amount, either two times (2X) or three times (3X), according to the ordering option. Only
those monitors ordered with this option will be affected. The Trip Multiply function is performed in
the System Monitor, but is an ordering option for each monitor. It must be specified at the time of
order placement and be installed at the factory.
Trip Multiply is activated by contact closure on the PIM. A red LED on the System Monitor front
panel indicates that the Trip Multiply function is active.